New Jersey Administrative Code
Title 14 - PUBLIC UTILITIES
Chapter 5 - ELECTRIC SERVICE
Subchapter 4 - METERS
Section 14:5-4.1 - Testing of electric meters

Universal Citation: NJ Admin Code 14:5-4.1

Current through Register Vol. 56, No. 6, March 18, 2024

(a) Each EDC furnishing electric service shall provide and have available a meter testing laboratory, standard meters and instruments, and such other equipment and facilities as may be necessary to make the tests required by these regulations, or by other orders of the Board.

(b) Each EDC furnishing electric service shall provide and have available such portable indicating electrical testing instruments and portable watt-hour meters of suitable range and type for testing service watt-hour meters, switchboard instruments, recording voltmeters and other electrical instruments in use as may be deemed necessary by the Board.

(c) For testing the accuracy of the portable watt-hour meters, commonly known as "rotating standards," and the portable instruments used for testing customers' service meters, each EDC shall provide and have available suitable indicating electrical instruments, watt-meters, watt-hour meters, or any or all of them hereinafter called "reference standards." Such standards may be of the service type of watt-hour meters, but, if so, such watt-hour meters shall be permanently mounted in the meter laboratory of the EDC and shall be used for no other purpose than for checking standards. All reference standards may be tested, adjusted and sealed by the Board at its discretion.

(d) All portable watt-hour meters (rotating standards) of the commutator type shall be compared with reference standards at least once each week. Every portable watt-hour meter (rotating standard) shall at all times be accompanied by a certificate giving the date when it was certified, the corrections to be applied at various loads, and signed by the proper authority. These certificates, when superseded, shall be kept on file in the office of the EDC at least one year.

(e) All portable, indicating electrical testing instruments, such as, voltmeters, ammeters and watt-meters, when in regular use for testing purposes, shall be checked against reference standards at least once a week when continuing in use.

(f) Instruments and standards may be tested and certified by any standardizing laboratory whose instruments and methods are approved by the Board.

Disclaimer: These regulations may not be the most recent version. New Jersey may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.