New Jersey Administrative Code
Title 13 - LAW AND PUBLIC SAFETY
Chapter 92 - MANUAL OF STANDARDS FOR JUVENILE DETENTION FACILITIES
Subchapter 4 - PHYSICAL STANDARDS
Section 13:92-4.6 - Sleeping rooms; new and renovated facilities
Current through Register Vol. 56, No. 18, September 16, 2024
(a) The sleeping areas of new or renovated detention facilities shall be provided by individual sleeping rooms which shall contain a minimum of 70 square feet of floor space, or double-occupancy sleeping rooms with a minimum of 100 square feet of floor space. No more than 20 percent of the capacity of new or renovated facilities shall be provided by double-occupancy sleeping rooms. Rooms shall not be approved for more than two occupants.
(b) In new or renovated sleeping rooms, suicide-resistant platform beds shall be provided and securely fastened to the wall and/or floor.
(c) All furnishings, fixtures and hardware in new or renovated sleeping rooms shall be suicide-resistant and approved for use by the Commission.
(d) All air vent covers and other grilles shall be designed to prevent suicide hanging attempts. Prototypes of all such grilles proposed for use shall be submitted to the Commission for review and approval.
(e) In new sleeping rooms, the following ceiling heights shall apply:
(f) Exterior glazing, of security grade, shall total a minimum of eight square feet of viewing area in new sleeping rooms and security screens shall be provided on operable windows.
(g) In new sleeping rooms, doors shall swing outward or slide sideways and contain a view panel with security glazing of at least 100 square inches to allow visual supervision of all parts of the room.