(a) Precautions at mixing plants shall include the following as provided by this section.
(b) Floors shall be constructed so as to eliminate floor drains and piping into which molten materials could flow and be confined in case of fire.
(c) The floors and equipment of the mixing and packaging room shall be cleaned regularly and thoroughly to prevent accumulation of oxidizers, fuels, or other sensitizers.
(d) The entire mixing and packaging building shall be cleaned regularly and thoroughly to prevent excessive accumulation of dust.
(e) Casual sources of ignition and firearms (except firearms carried by guards when authorized by police authorities) shall not be permitted inside of or within 50 feet of any building or facility used for the mixing of blasting agents.
(f) The land surrounding the mixing building shall be kept clear of brush, dried grass, leaves and other combustible materials for a distance of at least 25 feet.
(g) Empty ammonium nitrate bags shall be disposed of in a safe manner daily.
(h) No welding shall be permitted or open flames used in or around the mixing or storage area of the plant unless the equipment or area has been completely washed down and all oxidizing material removed.
(i) Before welding or repairs to hollow shafts, all oxidizing material shall be removed from the outside and inside of the shaft and the shaft vented with a minimum one half inch diameter opening.
(j) Explosives shall not be stored inside of or within 50 feet of any building or facility used for the mixing of blasting agents.