Current through Register Vol. 56, No. 18, September 16, 2024
(a) Precautions shall be
taken to prevent accidental discharge of electric blasting caps from current induced
by radar, radio transmitters, lightning, adjacent power lines, dust storms or other
sources of extraneous electricity.
1. All blasting
operations shall be suspended and all persons shall be removed from the blasting
area during the approach and progress of an electric storm.
2. Signs warning against the use of mobile radio
transmitters shall be posted on all roads within 350 feet of the blasting
operations.
3. The blaster shall comply
with Radio Frequency Radiation Hazards, IME No. 20-1978.
4. Before commencing blasting operations under
high voltage electric power lines or in other areas suspected of having extraneous
electric currents, the area shall be tested for extraneous electric current by a
competent person using an instrument designed for this purpose. Where extraneous
electric currents exceeding 0.05 ampere are found, the use of electric blasting is
prohibited.
5. When electric equipment
or energized power distribution circuits are within a horizontal distance of 25 feet
of the blast holes, the area shall be tested for extraneous electric current by a
competent person using an instrument designed for the purpose. Testing need not be
performed where the possible source of extraneous electric current is removed or
turned off. This provision shall not apply to overhead electric lines, when the
utility company gives approval to use electric blasting caps.
6. The leg wires of the electric blasting caps
shall be kept shunted unless being tested or wired into the blasting
circuit.
7. The firing line shall be
kept shunted until immediately prior to the time of hook-up to the blasting machine
or firing switch.
(b) Where
electric blasting caps are used under electric power lines, the firing line shall be
weighted down to prevent the line from coming in contact with the electric power
lines.
(c) Due precautions shall be
taken to ensure that the electric system will function properly.
1. All electric blasting caps in a single blast
shall be of the same type, same function, and of the same manufacturer.
2. Care shall be exercised to ensure that an
adequate quantity of delivered current is available in accordance with the
manufacturer's recommendations.
3. The
insulation on all electric lines to be used shall be adequate and in good condition
and kept from the contact with any electric conductor outside the electric blasting
circuitry.
4. The firing line shall be a
solid wire and have sufficient capacity to carry the firing current and have a
current carrying capacity of not less than No. 14 American Wire Gage copper
wire.
5. Electric blasting caps shall be
tested for continuity after the blast hole has been loaded and before the stemming
is added.
(d) Precautions
shall be taken in the sequence of wiring the blasting circuitry.
1. The wiring of the blasting circuitry shall not
commence until the work can proceed to completion without interruption.
2. The electric blasting cap leg wires shall be
connected and tested for continuity.
3.
The leg wires shall be connected to the connecting wires or bus wires and tested for
continuity.
4. The connection wires
shall be connected to the firing line and tested for continuity. The firing line
shall be reshunted.
5. All testing shall
be done by a blasting ohmmeter designed for this purpose. The ohmmeter shall be kept
in good condition and be periodically tested. A malfunctioning ohmmeter shall be
repaired by the manufacturer or the manufacturer's assigned representative when used
for this purpose.
(e) When
blasting with a blasting machine, the blasting machine shall be:
1. Designed specifically for this
purpose;
2. The rated capacity
needed;
3. In good working
condition;
4. Tested at least once a
month by procedures recommended by the manufacturer;
5. Repaired only by the manufacturer or a
competent person; and
6. Protected from
damage.
(f) Precautions shall
be taken when firing from a power line source.
1.
The firing circuitry shall not be grounded or placed where it can pick up the
extraneous electric current.
2. The
firing circuitry shall be a solid wire and have sufficient capacity to carry the
firing current and have a capacity of not less than No. 14 American Wire Gage copper
wire.
3. The insulation on all firing
lines shall be in good condition.
4.
When in a tunnel or other narrow passage, the firing line shall be placed on
insulators on the wall opposite other electric power lines.
5. There shall be a safety switch on each branch
firing line.
6. The main permanent
firing line shall be arranged to have a safety switch, at least a five foot
lightning gap, and a power switch.
7.
All switches for power circuits shall be the proper capacity, enclosed, capable of
being locked in the "off" or "open" position, and be distinctively
labeled.
8. The power source shall not
exceed 550 volts.
9. All switches shall
be kept locked unless firing a blast. The keys shall be entrusted only to the
blaster.