(a) Switchboards shall:

1. Have ample working area in back of them and all areas around the switchboard shall be kept free of rubbish and stored material.

2. Have an entrance at each end to permit inspection, adjustment or repairs to be made back of the switchboard.

3. Be adequately lighted.

4. Have control readily accessible for emergency shutdown.

5. Have disconnecting switch on incoming circuit at or near entrance to rear.

6. Have entrance to rear guarded against unauthorized entrance.

7. Be effectively grounded electrically if constructed of metal.

(b) Vertical clearance in the back of the switchboard shall be at least seven feet above the floor.

(c) Floor mats or platforms of insulating material shall be provided in front and back of every switchboard.

(d) Sufficient ventilation shall be provided at switchboards or switch panels to prevent overheating of electrical equipment.

Disclaimer: These regulations may not be the most recent version. New Jersey may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.