New Jersey Administrative Code
Title 10 - HUMAN SERVICES
Chapter 161B - STANDARDS FOR LICENSURE OF OUTPATIENT SUBSTANCE USE DISORDER TREATMENT FACILITIES
Subchapter 23 - PHYSICAL PLANT AND FUNCTIONAL REQUIREMENTS
Section 10:161B-23.11 - Attached structures

Universal Citation: NJ Admin Code 10:161B-23.11

Current through Register Vol. 56, No. 6, March 18, 2024

(a) Attached structures such as storage sheds or private garages located beneath the buildings shall have fire separation assemblies at the walls, floors, and ceilings separating the space from the adjacent interior enclosed space constructed of not less than one-hour fire resistance rating.

(b) Attached private garages shall be completely separated from the adjacent interior enclosed spaces and the attic area by means of one-hour fire rated separation assembly applied to the garage side.

(c) The sills of all door openings in the garage between garage and building shall be raised not less than four inches above the garage floor and openings shall be protected in accordance with the rules of the Department of Community Affairs at N.J.A.C. 5:23 and 5:70.

Disclaimer: These regulations may not be the most recent version. New Jersey may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.