New Hampshire Code of Administrative Rules
He - Department of Health and Human Services
Subtitle He-P - Former Division of Public Health Services
Chapter He-P 4000 - NEW HAMPSHIRE RULES FOR THE CONTROL OF RADIATION
Part He-P 4044 - RADIATION REQUIREMENTS FOR PARTICLE ACCELERATORS
Section He-P 4044.08 - Particle Accelerator Controls and Interlock Systems
Current through Register No. 40, October 3, 2024
(a) Instrumentation readouts and controls on the particle accelerator control console shall be clearly identified and easily discernible.
(b) Each entrance into a target room or other high radiation area shall be provided with a safety interlock that shuts down the machine under conditions of barrier penetration.
(c) When an interlock system has been tripped, it shall only be possible to resume operation of the accelerator by manually resetting controls at the position where the interlock has been tripped, and lastly at the main control console.
(d) Each safety interlock shall be on a circuit which shall allow its operation independently of all other safety interlocks.
(e) All safety interlocks shall be designed so that any defect or component failure in the safety interlock system prevents operation of the accelerator.
(f) A scram button or other emergency power cutoff switch shall be located and easily identifiable in all high radiation areas. Such a cutoff switch shall include a manual reset so that the accelerator cannot be restarted from the accelerator control console without resetting the cutoff switch.
#6827, eff 8-6-98; ss by #8692, INTERIM, eff 7-27-06, EXPIRES: 2-2-07; ss by #8808, eff 1-24-07