New Hampshire Code of Administrative Rules
Env - Department of Environmental Services
Subtitle Env-Ws - Division of Water
Chapter Env-Ws 300 - NEW HAMPSHIRE DRINKING WATER RULES
Part Env-Ws 380 - FILTRATION, DISINFECTION, TREATMENT PLANT AND WASTE RECYCLING
Section Env-Ws 380.14 - Monitoring Requirements for Systems That Do Not Provide Filtration
Current through Register No. 13, March 27, 2025
(a) The owner of a public water system that uses a surface water source and does not provide filtration treatment shall monitor as specified in this section.
(b) The owner of a public water system that uses a ground water source under the direct influence of surface water and does not provide filtration treatment shall monitor as specified in this section beginning 6 months after the department determines that the ground water source is under the direct influence of surface water unless the department has determined that filtration is required pursuant to Env-Ws 380.04, in which case the system shall monitor according to Env-Ws 375.10 until filtration is in place.
(c) Fecal coliform or total coliform density measurements shall be performed on representative source water samples immediately prior to the first or only point of disinfectant application as follows:
Table 380-1
Sampling Non-filtered Systems for Coliforms
System Size (persons served) (shall be taken on separate days) | Samples/Week |
<500 | 1 |
501 - 3,300 | 2 |
3,301 - 10,000 | 3 |
10,001 - 25,000 | 4 |
>25,000 | 5 |
(d) Turbidity measurements as required by Env-Ws 380.06 shall be performed on representative grab samples of source water immediately prior to the first or only point of disinfectant application every 4 hours, or more frequently, that the system serves water to the public.
(e) A public water system may substitute continuous turbidity monitoring for grab sample monitoring if it validates the continuous measurement for accuracy on a regular basis using a protocol recommended by the equipment manufacturer.
(f) The total inactivation ratio for each day that the system is in operation shall be determined based on the CT99.9 values in Tables 380-2 through Table 380-9 of Env-Ws 380.15, as applicable.
(g) The parameters necessary to determine the total inactivation ratio shall be monitored as follows:
(h) If the condition is not met as specified in (g) above, the system owner shall demonstrate, based on on-site studies or other information that the system is achieving at least 99.99 percent inactivation of viruses. CT values between the indicated temperatures shall be determined by linear interpolation. If no interpolation is used, the CT99.9 value at the lower temperature for determining CT99.9 values between indicated temperatures shall be used.
#5098, eff 3-18-91, EXPIRED 3-18-97
New. #6521, eff 6-4-97 (See Revision Note at chapter heading for Env-Ws 300); ss by #8352, eff 5-14-05 (formerly part of Env-Ws 380.22 )