New Hampshire Code of Administrative Rules
Env - Department of Environmental Services
Subtitle Env-Ws - Division of Water
Chapter Env-Ws 300 - NEW HAMPSHIRE DRINKING WATER RULES
Part Env-Ws 374 - DESIGN STANDARDS FOR LARGE PUBLIC WATER SYSTEMS
Section Env-Ws 374.07 - Safety Criteria for Chemical Additive(s) Proposal
Universal Citation: NH Admin Rules Env-Ws 374.07
Current through Register No. 13, March 27, 2025
(a) Safety criteria shall be as specified in this section.
(b) Treatment systems that add a chemical on a continuous basis shall have at least 2 of the methods identified in (c), below, to prevent a chemical overfeed.
(c) The following methods to prevent chemical overfeed shall be acceptable:
(1) Connection
of the electrical circuit of the chemical feed pump to the electrical circuit
of the main water pump;
(2)
Installation of a flow-measuring device with a common disconnect interfaced to
the circuit powering the chemical feed pump;
(3) Installation of a continuous-reading
analytical device for that particular chemical feed with a disconnect
interfaced to the chemical feed pump; or
(4) Any other method for which there is an
industry standard.
#8478, eff 11-30-05
Disclaimer: These regulations may not be the most recent version. New Hampshire may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.