New Hampshire Code of Administrative Rules
Env - Department of Environmental Services
Subtitle Env-Ws - Division of Water
Chapter Env-Ws 300 - NEW HAMPSHIRE DRINKING WATER RULES
Part Env-Ws 374 - DESIGN STANDARDS FOR LARGE PUBLIC WATER SYSTEMS
Section Env-Ws 374.06 - Design and Testing Criteria for Chemical Additive(s) Proposal

Universal Citation: NH Admin Rules Env-Ws 374.06

Current through Register No. 13, March 27, 2025

(a) Design and testing criteria for chemical additive(s) proposals shall be as specified in this section.

(b) The chemical(s) shall be applied under positive pressure conditions.

(c) Equipment shall be protected from siphon action with an approved anti-siphon device.

(d) A sampling point shall be provided that is at least 75 feet downstream of the point of injection and piped back to the injection station.

(e) Samples shall also be taken at locations throughout the distribution systems, as specified in the testing protocol submitted pursuant to Env-Ws 373.04(e).

(f) In addition to tests performed by the operator, samples from the system shall be submitted to the state laboratory as required by the department pursuant to Env-Ws 300.

(g) Daily records of testing and dosage shall be:

(1) Maintained as specified by the department pursuant to Env-Ws 300; and

(2) Submitted to the department on a monthly basis, no later than the 15th day of the month following the month for which the report is submitted.

#8478, eff 11-30-05

Disclaimer: These regulations may not be the most recent version. New Hampshire may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.