New Hampshire Code of Administrative Rules
Env - Department of Environmental Services
Subtitle Env-Ws - Division of Water
Chapter Env-Ws 300 - NEW HAMPSHIRE DRINKING WATER RULES
Part Env-Ws 373 - DESIGN STANDARDS FOR NON-COMMUNITY WATER SYSTEMS
Section Env-Ws 373.10 - Required Source Capacity
Current through Register No. 13, March 27, 2025
(a) The required minimum total source capacity for non-community water systems shall be not less than 1.5 times the design flow for the water system based on a 24-hour day.
(b) Since the design flows contained in Table 373-1 and Env-Ws 1008 do not include exterior water use, for those water systems where watering lawns and gardens, filling swimming pools, or other high water use demands are to be expected, additional source capacity for these uses shall be provided.
(c) For those NTNCwater systems whose reliability is directly important to public health as outlined in Env-Ws 373.02(c) that are required to have 2 or more wells, the minimum total permitted production volume with the largest source out of service shall be equal to or greater than 50% of the system's design flow.
(See Revision Note at chapter heading for Env-Ws 300); ss by #8499, eff 11-30-05