(a) The required minimum total source capacity for community water systems and those NTNC water systems whose reliability is directly important to public health as specified in Env-Ws 372.02(g) shall be not less than 2 times the design flow for the water system based on a 24-hour day.

(b) For small community water systems and NTNC water systems whose reliability is directly important to public health as specified in Env-Ws 372.02(g) that are required to have 2 or more wells, the minimum total permitted production volume with the largest source out of service shall be equal to or greater than 50% of the system's design flow.

(c) For all types of water systems, the minimum total permitted production volume shall not be less than the design flow for the water system.

(See Revision Note at chapter heading Env-Ws 300) #6521, eff 6-4-97; ss by #8360, INTERIM, eff 6-4-05, EXPIRES: 12-1-05; ss by #8496, eff 11-30-05

Disclaimer: These regulations may not be the most recent version. New Hampshire may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.