New Hampshire Code of Administrative Rules
Env - Department of Environmental Services
Subtitle Env-Ws - Division of Water
Chapter Env-Ws 300 - NEW HAMPSHIRE DRINKING WATER RULES
Part Env-Ws 364 - BACKFLOW PREVENTION
Section Env-Ws 364.07 - Replacement of Backflow Prevention Devices

Universal Citation: NH Admin Rules Env-Ws 364.07

Current through Register No. 13, March 27, 2025

(a) Any existing backflow prevention device shall be allowed to continue in service unless:

(1) The supplier considers the condition of any portion of the backflow prevention device to be such that replacement should be made; or

(2) The degree of hazard classification has changed so as to supersede the effectiveness of the present backflow prevention device currently in use.

(b) Water systems may grant one or more exemptions from this rulefor the replacement of existing backflow prevention devices to the customer, if:

(1) The exemption shall not result in an unreasonable risk to the public health; and

(2) The public water system or owner is unable to comply with the rule due to compelling factors, not including economic factors.

(c) An exemption shall not alter the degree of hazard classification of the cross-connection.

(d) Each exemption shall be conditioned on monitoring, testing, analyzing or other requirements to ensure the protection of the public health, and may include a deadline by which compliance shall be achieved.

(See Revision Note at chapter heading for Env-Ws 300) #6521, eff 6-4-97; ss by #8360, INTERIM, eff 6-4-05, EXPIRES: 12 -1-05 ; ss by #8476, eff 11-30-05

Disclaimer: These regulations may not be the most recent version. New Hampshire may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.