Section Env-Wq 1008.02 - System Capacity; Number of EDAs; Minimum Design Flow

Universal Citation: NH Admin Rules Env-Wq 1008.02

Current through Register No. 13, March 27, 2025

(a) The maximum allowable design capacity for an ISDS without a groundwater discharge permit as required under RSA 485-A:13 or RSA 485-C shall be 20,000 GPD.

(b) A system with design capacity of at least 2,500 GPD but no more than 5,000 GPD shall have at least 2 EDA separated by at least 10 feet, provided that the EDA may be a single field if a mounding analysis is submitted to show that the applicable separation distance to SHWT will be maintained.

(c) A system with a design capacity of more than 5,000 GPD shall have at least 2 EDA that are:

(1) Separated by at least 10 feet; and

(2) Each designed for a flow of not more than 5,000 GPD.

(d) No ISDS shall be designed to accommodate a sewage flow of less than 300 GPD, whether for commercial or non-commercial uses.

(See Revision Note at chapter heading for Env-Wq 1000) #9086, eff 2-9-08

Disclaimer: These regulations may not be the most recent version. New Hampshire may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.