Nevada Administrative Code
Chapter 645D - Inspectors of Structures
STANDARDS OF PRACTICE
Inspection of Structures
Section 645D.520 - Electrical systems

Universal Citation: NV Admin Code 645D.520

Current through September 16, 2024

1. A certified inspector shall inspect the electrical systems of the structure being inspected, including, but not limited to, the following components of the electrical system:

(a) The switches, receptacles and fixtures;

(b) The main panel box and all subpanel boxes, including, but not limited to, the feeders; and

(c) The readily accessible wiring and junction boxes.

2. An inspection of the electrical system must include, without limitation:

(a) An identification and description of the amperage and type of overcurrent protection devices, including, but not limited to, the fuses and breakers;

(b) A description of the condition of the electrical system, including, but not limited to, the grounding cables;

(c) A verification of the compatibility and condition of the main and branch circuit overcurrent protection devices to the size of the conductors served by them;

(d) The testing of a representative number of readily accessible switches, receptacles and light fixtures in each room or area of the structure;

(e) A test and verification of the grounding, polarity and operation of all readily accessible ground fault circuit interrupter devices; and

(f) An evaluation of the system and all readily accessible wiring.

Added to NAC by Real Estate Div. by R214-97, eff. 5-11-98; A by R177-01, 5-20-2002

NRS 645D.120

Disclaimer: These regulations may not be the most recent version. Nevada may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.