A barricade for a building or magazine containing explosives materials must effectively screen the building from the other buildings, public ways and magazines in the explosives manufacturing plant. A barricade that is made of mounds of revetted walls of earth must be not less than 3 feet in thickness. A barricade for a building or magazine containing explosives materials will be considered to be in compliance with this section if a straight line from the top of any side wall of the building or magazine to the eave line of any other building, or to a point that is 12 feet above the center line of a public way, passes through the barricade for the building or magazine.

Added to NAC by Div. of Industrial Relations by R109-00, eff. 9-6-2001

NRS 618.295, 618.890

Disclaimer: These regulations may not be the most recent version. Nevada may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.