Section 477.441 - General requirements
Current through December 12, 2024
1. A new or relocated portable building must:
2. Except as otherwise provided in this subsection, if two or more portable buildings are placed next to each other, there must be no empty spaces between the buildings. If it is physically impossible to place portable buildings next to each other so that there are no spaces between the portable buildings, the space between the portable buildings must have a barrier to prevent combustible materials or debris from entering that space.
3. Flammable or combustible material may not be stored beneath a portable building.
4. Portable buildings may not be joined if there are windows or other openings on the joined wall other than doors that are designed and used as access between the buildings.
5. Portable buildings which abut or are grouped together must not exceed the total area allowed by the International Building Code, 2018 edition, for occupancies which are designated as "Type V-B."
Added to NAC by St. Fire Marshal, eff. 2-17-94; A by R220-99, 9-25-2000; R062-04, 9-3-2004; R090-10, 12-30-2011; Added to NAC by St. Fire Marshal, eff. 2-17-94; A by R220-99, 9-25-2000; R062-04, 9-3-2004; R090-10, 12-30-2011; A by R123-13, eff. 1/16/2015; A by R132-18A, eff. 2/20/2020; A by R132-18CAP, eff. 12/16/2020