Nevada Administrative Code
Chapter 477 - State Fire Marshal
AUTOMATIC SPRINKLER SYSTEMS
Residential Systems
Section 477.490 - Plans required before installation or modification
Universal Citation: NV Admin Code 477.490
Current through December 12, 2024
1. Plans must be submitted to and approved by the authority having jurisdiction before any system is installed or modified. Plans must contain:
(a) The name of the company installing the system.
(b) The general location and exact address of the job location.
(c) A rough plot plan showing water supply and property lines in relation to the installation site.
(d) Water pressure at the installation site.
(e) A rough floor plan with system coverage indication.
(f) Any additional information required by the authority having jurisdiction.
2. The authority having jurisdiction may require additional plans, documentation of testing data, engineering specifications and equipment as deemed necessary.
[St. Fire Marshal, §§ 5.301 & 5.514, eff. 11-27-78]-(NAC A by R220-99, 9-25-2000; R062-04, 9-3-2004)
NRS 477.030
Disclaimer: These regulations may not be the most recent version. Nevada may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.