Section 461A.260 - Equipment for supplying electricity

Universal Citation: NV Admin Code 461A.260

Current through December 12, 2024

1. The equipment for supplying electricity to a mobile home must be capable of carrying a load of at least 100 amperes and must be capable of being connected permanently to the feeder assembly on the mobile home.

2. The service pedestal for supplying electricity to the mobile home must be equipped with receptacles which are:

(a) Of a plug-in type;

(b) Weatherproof;

(c) Capable of carrying a load of up to 50 amperes; and

(d) Equipped with fuses, circuit-breakers or other appropriate protection against excessive current.

3. In any mobile home park where natural gas is not available, the equipment which provides electricity to the mobile homes must be capable of carrying a load of at least 200 amperes.

4. Additional receptacles may be used for the connection of electric equipment located outside the mobile home, but each additional receptacle must be equipped with a ground fault circuit of the standard type for the protection of persons against accidental electric shock.

Added to NAC by Mfd. Housing Div., eff. 6-29-84

NRS 461A.090, 461A.230

Disclaimer: These regulations may not be the most recent version. Nevada may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.