Nevada Administrative Code
Chapter 459 - Hazardous Materials
STORAGE TANKS
Section 459.9948 - Underground storage tanks: Under-dispenser container required for certain motor fuel dispensers
Current through September 16, 2024
1. Except as otherwise provided in subsection 3, under-dispenser containment is required for all new fuel dispenser systems that are installed on or after July 1, 2008, at a location where there was no previous dispenser or at a location to replace an existing dispenser and the equipment used to connect the dispenser to the underground storage tank is replaced.
2. Under-dispenser containment must:
3. The Division may waive the requirements of this section if the owner or operator of a new fuel dispenser system demonstrates that the system is too large to be contained using a typical prefabricated containment sump, and the system is:
Added to NAC by Environmental Comm'n by R005-08, eff. 4-17-2008; A by R106-16A, eff. 11/2/2016
NRS 459.826, 459.830