Nevada Administrative Code
Chapter 459 - Hazardous Materials
STORAGE TANKS
Section 459.9945 - Underground storage tanks: Secondary containment system required on tank installed on or after July 1, 2008; exceptions

Universal Citation: NV Admin Code 459.9945

Current through September 16, 2024

1. Except as otherwise provided in subsection 2 , secondary containment is required for all underground storage tanks installed on or after July 1, 2008. Secondary containment for a new underground storage tank must meet the criteria for secondary containment set forth in 40 C.F.R. § 280.20.

2. The provisions of subsection 1 do not apply to underground storage tanks existing at a facility before July 1, 2008, which may be connected by piping or coupled through a manifold to the new underground storage tank.

Added to NAC by Environmental Comm'n by R005-08, eff. 4-17-2008; A by R106-16A, eff. 11/2/2016

NRS 459.826, 459.830

Disclaimer: These regulations may not be the most recent version. Nevada may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.