Nevada Administrative Code
Chapter 459 - Hazardous Materials
STORAGE TANKS
Section 459.9935 - Marina storage tanks: Secondary containment
Current through September 16, 2024
1. A marina storage tank must have a secondary containment area for the fuel stored in the tank.
2. Multiple products stored within the same containment area must be compatible with each other.
3. If the secondary containment area is open to precipitation, it must be capable of containing 110 percent of the capacity of the largest tank plus the volume displaced by the other tanks within the containment area.
4. The secondary containment area must be made of concrete or steel and be compatible with and impermeable to the products stored in the tank.
5. Liquid discharges to the environment from the secondary containment area are prohibited if contamination of the liquid by a regulated substance is suspected or detected.
6. The secondary containment area must not include any uncapped drain that extends outside of the containment area.
7. A double-walled tank does not require additional containment if:
Added to NAC by Environmental Comm'n by R083-05, eff. 10-31-2005
NRS 459.826, 459.830