Section 459.9934 - Marina storage tanks: Construction, design, location and overfill prevention

Universal Citation: NV Admin Code 459.9934

Current through September 16, 2024

1. A marina storage tank must meet the requirements of chapters 2, 22 and 34 of the International Fire Code , 2003 edition, with regard to construction, design, location and overfill prevention.

2. Any metallic portion of a marina storage tank or its piping system that is in contact with the soil or water and is subject to corrosion must be protected from corrosion by a continuously operating cathodic protection system that is properly engineered, installed and maintained in accordance with 40 C.F.R. §§ 280.20(a)(2) and 280.20(b)(2). A metal tank sitting on a concrete slab will be considered in contact with the soil unless it is insulated from the concrete by a dielectric material. Anchoring hardware is not considered part of the tank.

Added to NAC by Environmental Comm'n by R083-05, eff. 10-31-2005; A by R106-16A, eff. 11/2/2016

NRS 459.826, 459.830

Disclaimer: These regulations may not be the most recent version. Nevada may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.