Nevada Administrative Code
Chapter 452 - Cemeteries
Section 452.150 - Construction of crypts

Universal Citation: NV Admin Code 452.150

Current through February 27, 2024

1. All walls of crypts, unless built of granite or marble, must be constructed of concrete mixed with a proportion of at least one part cement, two and one-half parts sand, and three and one-half parts crushed rock or screen gravel.

2. All walls must be at least 4 inches in thickness and must be reinforced with steel.

3. Floor slabs of crypts must be at least 3 inches and must be reinforced with steel to conform to the specifications of a Class A construction.

4. No crypt may be constructed to be subject to any of the load strains of the structure of the building, except where the walls of the crypt or niche intersect or are a part of structural walls.

5. In mausoleums where air ventilation is used and crypts are situated adjacent to the wall of an outside building below the ground, an air space at least 18 inches wide must be provided between the outside wall and the walls of the crypt. The air space must be supplied with ventilation and must have one or more doorways at least 15 inches wide and 5 feet high.

Bd. of Health, part Mausoleum Reg., eff. 7-5-32

Disclaimer: These regulations may not be the most recent version. Nevada may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.