Nevada Administrative Code
Chapter 449 - Medical and Other Related Facilities
COMMUNITY TRIAGE CENTERS
Section 449.74369 - Service areas; miscellaneous requirements
Universal Citation: NV Admin Code 449.74369
Current through December 12, 2024
1. Each facility shall provide:
(a) A nursing station
which includes, without limitation:
(1) Space
for computer and printer equipment and for writing;
(2) A medication room or storage space for a
medication dispensing unit;
(3) A
separate utility room for clean materials;
(4) A separate utility room for soiled
materials;
(5) A break room for
staff;
(6) Separate toilet
facilities for staff; and
(7)
Lockers or secured storage for staff belongings;
(b) A separate room for secured storage of
patient belongings that have been determined to be hazardous;
(c) A separate room for the storage of clean
linen;
(d) A separate room for
nourishments that contains an ice machine, which must be self-dispensing if it
is accessible to patients or visitors;
(e) A treatment room which is at least 120
square feet and which includes, without limitation:
(1) A hand-washing sink with blade-type
handles or hands-free operation;
(2) A writing space;
(3) Sufficient lighting;
(4) Storage space for clean and sterile
supplies;
(5) Locked storage for
medications and double-locked storage for controlled substances in schedules I
to IV, inclusive, as described in chapter 453 of NRS;
(6) Cabinets for the storage of equipment;
and
(7) An examination table and a
chair for the use of patients;
(f) Flooring which is easy to clean and
intact, without cracks or holes;
(g) Insulation within the building to
conserve energy, protect personnel, prevent vapor condensation and reduce
noise;
(h) Air conditioning,
heating and ventilation to maintain a comfortable interior temperature;
and
(i) Laundry facilities to meet
the needs of the patients or, if the facility has a contract for linen
services, a room for receiving laundry. If the facility provides laundry
facilities, then those laundry facilities must be located in a room that is at
least 100 square feet. The room must be constructed of 1-hour
fire-resistant-rated construction, be fully equipped with sprinklers and have a
45-minute fire-resistant-rated door. The vents in the room must have fire and
smoke dampers installed in accordance with the requirements of NFPA
101: Life Safety Code, as adopted by reference pursuant to NAC
449.0105.
2. Each nursing station and each floor of the facility must have a janitors' room with a floor sink and backflow prevention. The janitors' room must:
(a) Provide
sufficient storage space for housekeeping chemicals and supplies, housekeeping
mops, brooms, service carts and cleaning supplies; and
(b) Be separate from any storage space used
for the storage of food.
3. Each facility shall have a procedure for the safe disposal of hazardous biological materials.
Added to NAC by Bd. of Health by R051-06, eff. 7-14-2006
NRS 449.0302
Disclaimer: These regulations may not be the most recent version. Nevada may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.