Section 445A.67245 - Cross-connections and backflow: Duties of certified backflow prevention assembly tester

Universal Citation: NV Admin Code 445A.67245

Current through September 16, 2024

A certified backflow prevention assembly tester shall:

1. Perform his or her field testing of assemblies for the prevention of backflow in accordance with the provisions of the Manual of Cross-Connection Control.

2. Use, for the testing of reduced pressure principle assemblies, double check valve assemblies and pressure vacuum breakers, a differential pressure gauge that has:

(a) A differential range of at least zero to 15 psi; and

(b) Graduations of not more than 0.2 psi.

3. Ensure that his or her testing equipment:

(a) Is calibrated to the manufacturers' specifications not less than annually; and

(b) Has all necessary hoses and fittings.

Added to NAC by Bd. of Health, eff. 2-20-97

NRS 445A.860

Disclaimer: These regulations may not be the most recent version. Nevada may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.