Nevada Administrative Code
Chapter 445A - Water Controls
PUBLIC WATER SYSTEMS
Design, Construction, Operation and Maintenance
Section 445A.67215 - Cross-connections and backflow: Service connection to fire sprinkler system
Current through September 16, 2024
1. A supplier of water shall ensure that:
The testing required by this subsection must be conducted by a certified backflow prevention assembly tester.
2. An assembly for the prevention of backflow installed on a service connection between a public water system and a fire sprinkler system must:
3. The supplier of water shall determine the type of assembly required on a particular service connection between the public water system and a fire sprinkler system based upon the degree of risk posed by the fire sprinkler system to the supply of potable water, considering the chemical and biological contents of the fire sprinkler system, the materials used to construct the fire sprinkler system and the possibility that backflow will occur.
4. Any reduced pressure principle assembly or reduced pressure detector assembly used on a service connection between a public water system and a fire sprinkler system must not have any holes drilled in the check valve clappers.
Added to NAC by Bd. of Health, eff. 2-20-97