Nevada Administrative Code
Chapter 445A - Water Controls
PUBLIC WATER SYSTEMS
Design, Construction, Operation and Maintenance
Section 445A.67205 - Cross-connections and backflow: Minimum types of protection for service connection to auxiliary supply of water or irrigation system
Universal Citation: NV Admin Code 445A.67205
Current through September 16, 2024
Except as otherwise provided in NAC 445A.67185 to 445A.67255, inclusive, the minimum type of protection required for a service connection to:
1. An auxiliary supply of water must consist of a double check valve assembly or reduced pressure principle assembly, as determined by the supplier of water and approved by the Division or the appropriate district board of health.
2. An irrigation system, including a system for irrigating median strips, must consist of:
(a) A pressure vacuum breaker or double check
valve assembly, as determined by the supplier of water and approved by the
Division or the appropriate district board of health; or
(b) Except as otherwise authorized by the
Division or the appropriate district board of health, if facilities have been
installed for pumping, injecting or applying fertilizers, pesticides or other
hazardous systems, a reduced pressure principle assembly.
Added to NAC by Bd. of Health, eff. 2-20-97; A by Environmental Comm'n by R194-08, 10-27-2009
NRS 445A.860
Disclaimer: These regulations may not be the most recent version. Nevada may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.