Section 445A.67185 - Cross-connections and backflow: General requirements

Universal Citation: NV Admin Code 445A.67185

Current through September 16, 2024

A supplier of water shall:

1. Ensure that there are no unprotected connections between the supplies of water, systems for the pumping, storage and treatment of water, and distribution system of the public water system and any source of pollution or contamination pursuant to which any unsafe water or other degrading material can be discharged or drawn into the public water system as a result of backsiphonage or backpressure.

2. Develop and carry out a program for the control of cross-connections that is approved by the Division or the appropriate district board of health. Except for a program that has been approved by the Division of Public and Behavioral Health or the appropriate district board of health before February 20, 1997, a program for the control of cross-connections must:

(a) Be submitted to the Division or the appropriate district board of health for its approval not later than:
(1) January 1, 1999; or

(2) Eighteen months after the public water system begins operation, whichever is later.

(b) Include:
(1) A schedule for implementation.

(2) A plan for inspecting the properties served by the public water system to determine the potential risk of cross-connection and backflow.

(3) A plan for testing and tracking all primary assemblies for the prevention of backflow which are intended to protect the public water system upstream from a service connection. The plan must provide for the annual testing of those assemblies and for the retention of records from that testing.

(4) A list of the particular assemblies for the prevention of backflow which may be used in the public water system or on service connections to the public water system.

(5) A list of the measures the supplier of water will take to enforce the program if any customers of the system fail to comply with the program.

(c) Ensure compliance with NAC 445A.67185 to 445A.67255, inclusive.

(d) Except as otherwise provided in NAC 445A.67185 to 445A.67255, inclusive, comply with the provisions of:
(1) The Uniform Plumbing Code, as adopted by reference in NAC 445A.6663;

(2) Manual of Water Supply Practices M14 Backflow Prevention and Cross-Connection Control: Recommended Practices, as adopted by reference in NAC 445A.6663; and

(3) The Manual of Cross-Connection Control, as adopted by reference in NAC 445A.6663.

If there is any conflict between any of the provisions described in this paragraph, the most stringent of those provisions prevails.

Added to NAC by Bd. of Health, eff. 2-20-97; A by Environmental Comm'n by R194-08, 10-27-2009; A by R118-14, eff. 12/22/2014; A by R104-22A, eff. 12/9/2022

NRS 445A.860

Disclaimer: These regulations may not be the most recent version. Nevada may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.