Nevada Administrative Code
Chapter 445A - Water Controls
PUBLIC WATER SYSTEMS
Design, Construction, Operation and Maintenance
Section 445A.6717 - Separation of lines: Sewer main crossing water service lateral
Current through September 16, 2024
1. Except as otherwise provided in subsection 2, if a sewer main crosses a water service lateral, the sewer main must be located at least 18 inches lower than the water service lateral, as measured vertically from the exterior walls of the pipes.
2. If compliance with subsection 1 is impracticable:
3. If a water service lateral is in place at the time a sewer main is constructed and must be relocated to comply with this section, the relocation must be performed:
4. The Division shall provide information regarding the process for proposing a modification pursuant to subsections 2 or 3 at the Internet website https://ndep.nv.gov/water/drinking-water/engineering-reviews.
Added to NAC by Bd. of Health, eff. 2-20-97; A by Environmental Comm'n by R194-08, 10-27-2009; A by R049-18A, eff. 8/21/2018