Nevada Administrative Code
Chapter 445A - Water Controls
PUBLIC WATER SYSTEMS
Design, Construction, Operation and Maintenance
Section 445A.67155 - Separation of lines: Sewer main parallel to water main or water service lateral
Universal Citation: NV Admin Code 445A.67155
Current through September 16, 2024
1. If a sewer main parallels a water main or water service lateral:
(a) Whenever possible, the sewer main must be
located lower than the water main or water service lateral.
(b) Except as otherwise provided in paragraph
(c), the sewer main must be in a separate trench and:
(1) Located at least 10 feet away from the
water main or water service lateral, as measured horizontally from the exterior
walls of the pipes;
(2) If
compliance with subparagraph (1) is not practicable, located:
(I) At least 5 feet away from the water main
or water service lateral, as measured horizontally from the exterior walls of
the pipes; and
(II) At least 18
inches lower than the water main or water service lateral, as measured
vertically from the exterior walls of the pipes; or
(3) If compliance with neither subparagraph
(1) nor subparagraph (2) is practicable, located at least 6 feet away from the
water main or water service lateral, as measured horizontally from the exterior
walls of the pipes. If the sewer main:
(I) Is
in place at the time a water project is performed, the sewer main must be
totally encased in at least 4 inches of cement slurry.
(II) Is not in place at the time a water
project is performed, the sewer main must be constructed of PVC with joints
that comply with Standard D3212 of the American Society for Testing and
Materials.
(c) If compliance with the requirements set
forth in subparagraph (b) is not practicable, an engineer must:
(1) Identify in the plans the area where
compliance is impracticable in plan and profile views;
(2) Provide any applicable standard details
for the area where compliance is impracticable;
(3) Propose a modification to the
requirements;
(4) Demonstrate that
the modification will not conflict with the provisions of NAC
445A.66615; and
(5) Request approval from the Division or the
appropriate district board of health for the engineer's proposed
modification.
2. The Division shall provide information regarding the process for proposing a modification pursuant to paragraph (c) at the Internet website https://ndep.nv.gov/water/drinking-water/engineering-reviews.
Added to NAC by Bd. of Health, eff. 2-20-97; A by R049-18A, eff. 8/21/2018
NRS 445A.860
Disclaimer: These regulations may not be the most recent version. Nevada may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.