Section 445A.67135 - Distribution system: Release and blowoff valves
Current through September 16, 2024
1. Air and vacuum valves, air release valves or hydrants must be installed at high points in water mains where air tends to accumulate.
2. Suitably sized blowoff valves must be provided in appropriate locations at low points in water mains with diameters of 20 inches or more. Blowoff valves must have air gaps and must not discharge directly into sewer lines.
3. Except as otherwise provided in subsection 4, the openings of any vents in a valve required pursuant to this section must:
4. If compliance with subsection 3 is impracticable, the Division or the appropriate district board of health may, on a case-by-case basis, authorize below-grade openings in vents. If so authorized:
Added to NAC by Bd. of Health, eff. 2-20-97; A by Environmental Comm'n by R194-08, 10-27-2009