Nevada Administrative Code
Chapter 445A - Water Controls
PUBLIC WATER SYSTEMS
Design, Construction, Operation and Maintenance
Section 445A.6707 - Storage structures: Clear wells

Universal Citation: NV Admin Code 445A.6707

Current through September 16, 2024

1. Clear wells must be sized in conjunction with any distribution storage in such a manner that the components of the public water system for the acquisition and treatment of water will not be required directly to follow fluctuations in the use of water or directly to meet maximum day demand and peak hour demand.

2. The capacity of a clear well must be sufficient to provide for the storage of the amount of finished water required for:

(a) Backwashing;

(b) Equalizing the storage of water necessary for the high-service pumping station of a treatment facility; and

(c) The operation of a treatment facility, if necessary.

3. Finished water must not be stored or conveyed in a compartment that is adjacent to a compartment of untreated water unless the two compartments are separated by more than a single wall.

4. If a clear well is used to provide the period of contact required for disinfection, the clear well must be designed in such a manner that it is of the appropriate size and has such baffles as are necessary to accomplish that function.

5. Clear wells must be designed in such a manner as to assist the public water system in maintaining its total capacity when filters or processes for treatment fail.

Added to NAC by Bd. of Health, eff. 2-20-97

NRS 445A.860

Disclaimer: These regulations may not be the most recent version. Nevada may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.