Section 445A.67035 - Pumping facilities: Gauges and meters

Universal Citation: NV Admin Code 445A.67035

Current through September 16, 2024

1. Except as otherwise provided in subsection 4, each pump must:

(a) Have a permanent standard pressure gauge on its discharge line located upstream from any check valve.

(b) Except for a vertical turbine pump, have a:
(1) Permanent standard pressure gauge on its suction line if the pump is in suction head; or

(2) Permanent compound pressure gauge on its suction line if the pump is in suction lift.

2. Each pumping station must have a device for measuring the rate of flow of discharge and the total flow.

3. A meter or flow sensor must have straight pipes installed both upstream and downstream. The length of the pipes must:

(a) Comply with the specifications of the manufacturer of the meter or flow sensor; or

(b) In the absence of those specifications, be at least five times the diameter of the pipes.

4. In lieu of a permanent standard or compound pressure gauge required by subsection 1, a pump may have a connection for a temporary pressure gauge and a pressure transducer with a local or remote indicator. A temporary pressure gauge installed pursuant to this subsection must be maintained on-site.

Added to NAC by Bd. of Health, eff. 2-20-97; A by R104-22A, eff. 12/9/2022

NRS 445A.860

Disclaimer: These regulations may not be the most recent version. Nevada may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.