1. Priming must be conducted in such a manner that:

(a) The water used for priming is of no less a sanitary quality than that of the water being pumped.

(b) There is a means to prevent backflow.

(c) In installations where a centrifugal pump is used and air binding or the accumulation of air is a problem, there is a means to remove the air from the eye of the impeller.

(d) Where vent lines discharge to a drain, the vent lines are designed with an air gap.

2. This section does not prohibit the use of self-priming pumps.

Added to NAC by Bd. of Health, eff. 2-20-97

NRS 445A.860

Disclaimer: These regulations may not be the most recent version. Nevada may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.