Nevada Administrative Code
Chapter 445A - Water Controls
PUBLIC WATER SYSTEMS
Design, Construction, Operation and Maintenance
Section 445A.66955 - Springs: Covering of device for collection of water
Current through September 16, 2024
Except as otherwise justified by an engineer and approved by the Division or the appropriate district board of health, a device for the collection of water from a spring which is used as a source of water for a public water system, whether the device consists of collection tile, perforated PVC, infiltration boxes or tunnels, must be:
1. Covered with a minimum of 10 feet of impervious soil cover that extends a minimum of 15 feet in all horizontal directions up gradient from the device for the collection of water; or
2. Where it is impossible to comply with the requirements of subsection 1, covered with an impermeable liner. If an impermeable liner is necessary:
If warranted by the physical circumstances of a particular spring, the Division or the appropriate district board of health may require more stringent criteria for the design of an impermeable liner than the criteria set forth in this subsection.
Added to NAC by Bd. of Health, eff. 2-20-97; A by Environmental Comm'n by R194-08, 10-27-2009
NRS 445A.860