Nevada Administrative Code
Chapter 445A - Water Controls
MINING FACILITIES
Operation and Design of Facilities
Section 445A.436 - Minimum design criteria: Vats, tanks and other containers which confine process fluids

Universal Citation: NV Admin Code 445A.436
Current through September 16, 2024

Vats, tanks and other containers which confine process fluids and can be inspected for leaks visually do not require double liners if an area for secondary containment equal to 110 percent of the largest container is provided. Vats, tanks or other containers that are partially buried and cannot be visually inspected must have a system to detect leaks.

Added to NAC by Environmental Comm'n, eff. 9-1-89-Substituted in revision for NAC 445.24366

NRS 445A.425, 445A.465

Disclaimer: These regulations may not be the most recent version. Nevada may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.