Nevada Administrative Code
Chapter 444 - Sanitation
RECYCLING OF USED ANTIFREEZE
General Requirements
Section 444.8891 - Above-ground storage tank: Secondary system for containment

Universal Citation: NV Admin Code 444.8891

Current through September 16, 2024

1. Each storage tank that is above the ground which stores used antifreeze at a facility for the transfer of used antifreeze or a facility for the recycling of used antifreeze must have a secondary system for containment which:

(a) Includes dikes, berms or retaining walls, or the equivalent, which are impervious to the penetration of used antifreeze;

(b) Except as otherwise provided in subsection 2, includes a floor, or the equivalent, which covers the entire area within the dike, berm or retaining wall and is impervious to the penetration of used antifreeze; and

(c) Is large enough to prevent the release of used antifreeze into the soil, groundwater or surface water.

2. If a storage tank that is above the ground is being used as of October 3, 1996, the floor of the secondary system for containment is not required to cover that portion of the tank which has contact with the ground.

Added to NAC by Environmental Comm'n, eff. 10-3-96

NRS 459.485

Disclaimer: These regulations may not be the most recent version. Nevada may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.