Nebraska Administrative Code
Topic - LABOR, DEPARTMENT OF
Title 229 - DEPARTMENT OF LABOR
Chapter 23 - MINIATURE BOILERS - EXISTING INSTALLATIONS
Section 229-23-009

Current through March 20, 2024

Miniature boilers shall be provided with at least one feed pump or other feeding device, except where it is connected to a water main carrying sufficient pressure to feed the boiler or where it is operated with no extraction of steam (closed system). In the latter case, in lieu of a feeding device, a suitable connection or opening shall be provided to fill the boiler when cold. Such connection shall be no less than one-half inch NPS for iron or steel pipe and one-fourth inch for brass or copper pipe.

Disclaimer: These regulations may not be the most recent version. Nebraska may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.