Nebraska Administrative Code
Topic - LABOR, DEPARTMENT OF
Title 229 - DEPARTMENT OF LABOR
Chapter 21 - POWER BOILERS - EXISTING INSTALLATIONS
Section 229-21-036

Current through March 20, 2024

Each steam boiler shall have a steam gauge connected to the steam space or to the steam connection to the water column. The steam gauge shall be connected to a siphon or equivalent device of sufficient capacity to keep the gauge tube filled with water. The gauge shall be arranged so that it cannot be shut off from the boiler except by a cock placed near the gauge. A tee or lever handle shall be parallel to the pipe in which it is located when the cock is open.

Disclaimer: These regulations may not be the most recent version. Nebraska may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.