Chapter 21 - POWER BOILERS - EXISTING INSTALLATIONS
Section 229-21-028

Current through March 20, 2024

Each steam outlet from a boiler, except safety valve and water column connections, shall be fitted with a stop valve located as close as practicable to the power boiler. When a stop valve is so located that water can accumulate, ample drains shall be provided. The drainage shall be piped to a safe location and shall not be discharged on the top of the power boiler or its setting.

Disclaimer: These regulations may not be the most recent version. Nebraska may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.