Chapter 20 - POWER BOILERS - NEW INSTALLATIONS
Section 229-20-007
Universal Citation: 229 NE Admin Rules and Regs ch 20 ยง 007
Current through March 20, 2024
One or more safety valves on every power boiler shall be set at or below the maximum allowable working pressure. The remaining valves may be set within a range of three percent above the maximum allowable working pressure but, the range setting of all the safety valves on a power boiler shall not exceed ten percent of the highest pressure at which any valve is set.
Disclaimer: These regulations may not be the most recent version. Nebraska may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.