007.02 Monitoring Requirements
Monitoring for the contaminants listed in 179 NAC
2-002.04B1 (VOC)
for purposes of determining compliance with the maximum contaminant levels must
be conducted as follows.
3-007.02A
Ground Water Sources: Ground water sources must be
monitored at every entry point to the distribution system which is
representative of each ground water source after treatment (hereafter called a
sampling point or entry point). Each sample must be taken at the same sampling
point unless conditions make another sampling point more representative of each
source, treatment plant, or within the distribution system.
3-007.02B
Surface Water
Sources: Surface water sources (or combined surface/ground water
sources) must take a minimum of one sample at points in the distribution system
that are representative of each source or at each entry point to the
distribution system after treatment (hereafter called a sampling point or entry
point). Each sample must be taken at the same sampling point unless conditions
make another sampling point more representative of each source, treatment
plant, or within the distribution system.
3-007.02C
Multiple
Sources: If an entry point represents more than one source and the
sources are combined before distribution, the system owner must sample at an
entry point to the distribution system during periods of normal operating
conditions (i.e., when water representative of all sources is being
used).
3-007.02D
Monitoring Frequency: Each community and non-transient,
non-community water system must take four consecutive quarterly samples for
each contaminant listed in 179 NAC
2-002.04B during
each compliance period, beginning in the initial compliance period.
3-007.02E
If No Contaminant Is
Detected: If the initial monitoring for contaminants listed in 179
NAC
2-002.04B1 (1) through
(8) and the monitoring for the contaminants
listed in 179 NAC
2-002.04B1 (9) through
(21) was completed by December 31, 1992, and
the system did not detect any contaminant listed in 179 NAC
2-002.04B1 (1) through
(21), then each ground and surface water
system must take one sample annually beginning with the initial compliance
period.
3-007.02F
Reduced VOC Monitoring: After a minimum of three years
of annual sampling, the Director may allow ground water systems with no
previous detection of any contaminant listed in 179 NAC
2-002.04B1 to take
one sample during each compliance period.
3-007.02G
Waiver:
The owner of each community and non-transient, non-community ground water entry
point, at which no contaminant listed in 179 NAC
2-002.04B1 is
detected, may apply to the Director for a waiver from the requirements of 179
NAC
3-007.02E and
3-007.02F after
completing the initial monitoring. (For the purposes of 179 NAC
3-007.02G,
detection is defined as >= 0.0005 mg/L.) A waiver will be effective for no
more than six years (two compliance periods). The Director may also issue
waivers to small systems for the initial round of monitoring for
1,2,4-trichlorobenzene.
3-007.02H
Bases of a Sampling Waiver: The Director may grant a
waiver after evaluating the following factor(s):
1. Knowledge of previous use (including
transport, storage, or disposal) of the contaminant within the watershed or
zone of influence of the system. If a determination by the Director reveals no
previous use of the contaminant within the watershed or zone of influence, a
waiver may be granted.
2. If
previous use of the contaminant is unknown or it has been used previously, then
the following factors must be used to determine whether a waiver is granted:
a. Previous analytical results;
b. The proximity of the sources for the entry
point to a potential point or non-point source of contamination (point sources
include spills and leaks of chemicals at or near a water treatment facility or
at manufacturing, distribution, or storage facilities, or from hazardous and
municipal waste landfills and other waste handling or treatment
facilities);
c. The environmental
persistence and transport of the contaminants;
d. The number of individuals served by the
public water system and the proximity of a small system to a larger
system;
e. How well the water
source is protected against contamination, such as whether it is a surface or
ground water system. (For ground water sources, the Director will consider
factors such as depth of the well, the type of soil, and wellhead protection.
For surface water sources, the Director will consider watershed
protection.)
3-007.02I As a condition of the waiver, the
owner of a ground water system must take one sample at an entry point which
received a waiver during the time the waiver is effective (i.e., one sample
during two compliance periods or six years) and update its vulnerability
assessment considering the factors listed in 179 NAC
3-007.02H. Based
on this vulnerability assessment, the Director will reconfirm that the entry
point is non-vulnerable. If the Director does not make this reconfirmation
within three years of the initial determination, then the waiver is
invalidated.
3-007.02J The owner of
each community and non-transient, non-community surface water entry point, at
which no contaminant listed in 179 NAC
2-002.04B1 is
detected, may apply to the Director for a waiver from the requirements of 179
NAC
3-007.02E after
monitoring at least one time. (For the purposes of this section, detection is
defined as >= 0.0005 mg/L.) Composite samples from a maximum of five
sampling points are allowed, provided that the detection limit of the method
used for analysis is less than one-fifth of the MCL. Entry points meeting this
criterion must be determined by the Director to be non-vulnerable based on a
vulnerability assessment during each compliance period. Each system receiving a
waiver must sample at the frequency specified by the Director (if
any).
3-007.02K If a contaminant in
179 NAC
2-002.04B1 (1) through
(21) is detected at a level exceeding 0.0005
mg/L in any sample, for the first time, then:
1. The owner of the system must monitor
quarterly at each sampling point which resulted in a detection.
2. The Director may decrease the quarterly
monitoring requirement specified in 179 NAC
3-007.02K item 1
provided it has determined that the system is reliably and consistently below
the maximum contaminant level. In no case will the Director make this
determination unless a ground water system takes a minimum of two quarterly
samples and a surface water system takes a minimum of four quarterly
samples.
3. If the Director
determines that the system is reliably and consistently below the MCL, the
Director may allow the system to monitor annually. Systems that monitor
annually must monitor during the quarter(s) that previously yielded the highest
analytical result.
4. Systems that
have three consecutive annual samples with no detection of a contaminant may
apply to the Director for a waiver as specified in 179 NAC
3-007.02G.
5.
Vinyl Chloride
Monitoring: Analysis for vinyl chloride is required only for
ground water systems that have detected one or more of the following two-carbon
organic compounds: Trichloroethylene, tetrachloroethylene, 1,2-dichloroethane,
1,1,1-trichloroethane, cis-1,2-dichloroethylene, trans-1, dichloroethylene, or
1,1-dichloroethylene. The analysis for vinyl chloride is required at each
distribution or entry point at which one or more of the two-carbon organic
compounds were found. If the first analysis does not detect vinyl chloride, the
Director may reduce the frequency of vinyl chloride monitoring to one every
three years for that sample location or other sample locations which are more
representative of the same source. Surface water systems may be required to
analyze for vinyl chloride at the discretion of the Director.
3-007.02L Entry points which
violate the requirements of 179 NAC
2-002.04B1, as
determined by 179 NAC
3-007.02O, must
monitor quarterly. After a minimum of four consecutive quarterly samples which
show the entry point is in compliance and the Director determines that the
entry point is reliably and consistently below the maximum contaminant level,
the owner of the entry point may monitor at the frequency and time specified in
179 NAC
3-007.02K item
3.
3-007.02M The Director may
require confirmation samples for positive or negative results. If a
confirmation sample(s) is required by the Director, then the sample result(s)
must be averaged with the first sampling result and the average used for
compliance determination in accordance with 179 NAC
3-007.02O. The
Director has discretion to delete results of obvious sampling errors from this
calculation.
3-007.02N
Composite Samples: The Director may reduce the total
number of samples a system must analyze by allowing the use of compositing.
Composite samples from a maximum of five sampling points are allowed, provided
that the detection limit of the method used for analysis is less than one-fifth
of the MCL. Compositing of samples is to be done in the laboratory by the
procedures listed below. Samples must be analyzed within 14 days of collection.
1. If the concentration in the composite
sample is greater than or equal to 0.0005 mg/L for any contaminant listed in
179 NAC
2-002.04B1, then a
follow-up sample must be taken and analyzed within 14 days from each sampling
point included in the composite.
2.
If duplicates of the original sample taken from each sampling point used in the
composite are available, the system owner may use these duplicates instead of
resampling. The duplicate must be analyzed within 14 days of
collection.
3. If the population
served by the system is greater than 3,300 individuals, then compositing may
only be permitted at sampling points within a single system. In systems serving
less than or equal to 3,300 individuals, compositing among different systems is
allowed provided the 5-sample limit is maintained.
4.
Compositing Samples prior to
GC Analysis
a. Add 5 ml or equal
larger amounts of each sample (up to 5 samples are allowed) to a 25 ml glass
syringe. Special precautions must be made to maintain zero headspace in the
syringe.
b. The samples must be
cooled at 4°C during this step to minimize volatilization losses.
c. Mix well and draw out a 5-ml aliquot for
analysis.
d. Follow sample
introduction, purging and desorption steps described in the method.
e. If less than five samples are used for
compositing, a proportionately smaller syringe may be used.
5.
Compositing Samples
Prior to GC/MS Analysis
a.
Inject 5-ml or equal larger amounts of each aqueous sample (up to 5 samples are
allowed) into a 25-ml purging device using the sample introduction technique
described in the method.
b. The
total volume of the sample in the purging device must be 25 ml.
c. Purge and desorb as described in the
method.
3-007.02O
Compliance
Calculations: Compliance with the MCL in 179 NAC
2-002.04B1 will be
determined based on the analytical results obtained at each sampling point. If
one sampling point is in violation of an MCL, the system is in violation of the
MCL.
1. For systems monitoring more than once
per year, compliance with the MCL is determined by a running annual average at
each sampling point.
2. Systems
monitoring annually or less frequently whose sample result exceeds the MCL must
begin quarterly sampling. The system will not be considered in violation of the
MCL until it has completed one year of quarterly sampling.
3. If any sample result will cause the
running annual average to exceed the MCL at any sampling point, the system is
out of compliance with the MCL immediately.
4. If a system fails to collect the required
number of samples, compliance will be based on the total number of samples
collected.
5. If a sample result is
less than the detection limit, zero will be used to calculate the annual
average.
3-007.02P
Certified and Approved Laboratories: Analysis under
179 NAC 3-007 must only be conducted by the Department of Health and Human
Services Public Health Environmental Laboratory or other laboratories that are
certified by the Department or EPA according to the following conditions.
1. To receive certification to conduct
analyses for the contaminants in 179 NAC
2-002.04B1 (2) through
(21), the laboratory must:
a. Analyze Performance Evaluation (PE)
samples which include these substances provided by EPA Environmental Monitoring
and Support Laboratory or equivalent samples provided by the Director at least
once a year by each method for which the lab desires certification.
b. Achieve the following quantitative
acceptance limits under 179 NAC
3-007.02P items
1.c. and 1.d. for at least 80% of the regulated organic chemicals included in
the PE sample.
c. Achieve
quantitative results on the analyses performed under 179 NAC
3-007.02P item
1.a. that are within ±20% of the actual amount of the substances in the
Performance Evaluation sample when the actual amount is greater than or equal
to 0.010 mg/L.
d. Achieve
quantitative results on the analyses performed under 179 NAC
3-007.02P item
1.a. that are within ±40% of the actual amount of the substances in the
Performance Evaluation sample when the actual amount is less than 0.010
mg/L.
e. Achieve a method detection
limit of 0.0005 mg/L, according to the procedures in Appendix B to Part 136 of
the Code of Federal Regulations.
2. To receive certification to conduct
analyses for vinyl chloride, the laboratory must:
a. Analyze Performance Evaluation (PE)
samples provided by EPA Environmental Monitoring and Support Laboratory or
equivalent samples provided by the Director at least once a year by each method
for which the laboratory desires certification.
b. Achieve quantitative results on the
analyses performed under 179 NAC
3-007.02P item
2.a. that are within ±40% of the actual amount of vinyl chloride in the
Performance Evaluation sample.
c.
Achieve a method detection limit of 0.0005 mg/L, according to the procedures in
Appendix B to Part 136 of the Code of Federal Regulations.
d. Obtain certification for the contaminants
listed in 179 NAC
2-002.04B1 (2) through
(21).
3-007.02Q The Director may increase required
monitoring where necessary to detect variations within the system.
3-007.02R
Laboratory
Certification: Each approved laboratory must determine the method
detection limit (MDL), (as defined in Appendix B to Part 136 of the Code of
Federal Regulations. at which it is capable of detecting VOCs. The acceptable
MDL is 0.0005 mg/L. This concentration is the detection concentration for
purposes of 179 NAC 3-007.
3-007.02S
State Designated VOC
Sampling Schedules: Each public water system owner must monitor at
the time designated by the Director within each compliance period.
3-007.02T
New Systems Or
Sources: All new systems or systems that use a new source of water
that begin operation after January 22, 2004 must demonstrate compliance with
the MCL within a period of time specified by the Director. The system must also
comply with the initial sampling frequencies specified by the Director to
ensure a system can demonstrate compliance with the MCL. Routine and increased
monitoring frequencies must be conducted in accordance with the requirements in
179 NAC 3-007.
007.03
Monitoring Sites and Protocol
Analysis of the contaminants listed in 179 NAC
2-002.04B2 for the
purposes of determining compliance with the maximum contaminant level must be
conducted as follows:
1.
Ground Water Sources: Ground water sources must be
monitored at every entry point to the distribution system which is
representative of each ground water source after treatment (hereafter called a
sampling point or entry point). Each sample must be taken at the same sampling
point unless conditions make another sampling point more representative of each
source or treatment plant.
2.
Surface Water Sources: Surface water sources must be
monitored at points in the distribution system that are representative of each
source or at each entry point to the distribution system after treatment
(hereafter called a sampling point or entry point). Each sample must be taken
at the same sampling point unless conditions make another sampling point more
representative of each source or treatment plant.
NOTE: For the purposes of 179 NAC 3-007.03 item 2, surface
water systems include systems with a combination of surface and ground water
sources.
3.
Multiple Sources: If an entry point represents more
than one source and the sources are combined before distribution, the system
owner must sample at the entry point to the distribution system during periods
of normal operating conditions (i.e., when water representative of all sources
is being used).
4.
Monitoring Frequency
a.
Initial Compliance Period
Monitoring: Owners of each community and non-transient,
non-community water system must take four consecutive quarterly samples during
the three-year compliance period which ends December 31, 1995 for each
contaminant listed in 179 NAC
2-002.04B2 during
the compliance period which began January 1, 1996 and ended December 31,
1998.
b.
Repeat
Compliance Period Monitoring: Systems serving more than 3,300
individuals that do not detect a contaminant in the initial compliance period
may reduce the sampling frequency to a minimum of two quarterly samples in one
year during each repeat compliance period.
c. Systems serving less than or equal to
3,300 individuals that do not detect a contaminant in the initial compliance
period may reduce the sampling frequency to a minimum of one sample during each
repeat compliance period.
5.
Waivers from Initial and
Repeat Compliance Period Monitoring: A system owner may apply to
the Director for a waiver from the requirements in 179 NAC 3-007.03 item 4. A
system owner must reapply for a waiver for each compliance period.
6. The Director may grant a waiver after
evaluating the following factor(s): Knowledge of previous use (including
transport, storage, or disposal) of the contaminant within the watershed or
zone of influence of the entry point source(s). If a determination by the
Director reveals no previous use of the contaminant within the watershed or
zone of influence, a waiver may be granted. If previous use of the contaminant
is unknown or it has been used previously then the following factors will be
used to determine whether a waiver is granted:
a. Previous analytical results.
b. The proximity of the entry point source(s)
to a potential point or non-point source of contamination. Point sources
include spills and leaks of chemicals at or near a water treatment facility or
at manufacturing, distribution, or storage facilities, or from hazardous and
municipal waste landfills and other waste handling or treatment facilities.
Non-point sources include use of pesticides to control insect and weed pests on
agricultural areas, forest lands, home and gardens, and other land application
uses.
c. The environmental
persistence and transport of the pesticide or PCBs.
d. How well the water source is protected
against contamination due to such factors as depth of the well and the type of
soil and the integrity of the well casing.
e. Elevated nitrate levels at the entry point
source(s).
f. Use of PCBs in
equipment used in the production, storage, or distribution of water (i.e., PCBs
used in pumps, transformers, etc.).
7.
If Detected: If
an organic contaminant listed in 179 NAC
2-002.04B2 is
detected (as defined by 179 NAC 3-007.03 item 17) in any sample, then:
a. The owner must monitor quarterly at each
sampling point which resulted in a detection for each contaminant which was
detected.
b. The Director may
decrease the quarterly monitoring requirement specified in 179 NAC 3-007.03
item 7.a. provided it has determined that the system is reliably and
consistently below the maximum contaminant level. In no case will the Director
make this determination unless a ground water system takes a minimum of two
quarterly samples and a surface water system takes a minimum of four quarterly
samples.
c. After the Director
determines the system is reliably and consistently below the maximum
contaminant level, the Director may allow the system to monitor annually.
Systems that monitor annually must monitor during the quarter that previously
yielded the highest analytical result.
d. Systems that have three consecutive annual
samples with no detection of a contaminant may apply to the Director for a
waiver as specified in 179 NAC 3-007.03 item 6.
e. If monitoring results in detection of one
or more of certain related contaminants (aldicarb, aldicarb sulfone, aldicarb
sulfoxide and heptachlor, heptachlor epoxide), then subsequent monitoring must
analyze for all related contaminants.
8.
MCL Violation and
Reliably/Consistently Below the MCL: Entry points which violate an
MCL in 179 NAC
2-002.04B2 as
determined by 179 NAC 3-007.03 item 11 must monitor quarterly. After a minimum
of four quarterly samples show the system is in compliance and the Director
determines the entry point is reliably and consistently below the MCL, as
specified in 179 NAC 3-007.03 item 11, the system owner must monitor the entry
point at the frequency specified in 179 NAC 3-007.03 item 7.c.
9.
Confirmation
Sampling: The Director may require a confirmation sample for
positive or negative results. If a confirmation sample is required by the
Director, the result must be averaged with the first sampling result and the
average used for the compliance determination as specified in 179 NAC 3-007.03
item 11. The Director has the discretion to delete results of obvious sampling
errors from this calculation.
10.
Composite Sampling: The Director may reduce the total
number of samples a system must analyze by allowing the use of compositing.
Composite samples from a maximum of five sampling points are allowed, provided
that the detection limit of the method used for analysis is less than one-fifth
of the MCL. Compositing of samples must be done in the laboratory and analyzed
within 14 days of sample collection.
a. If the
concentration in the composite sample detects one or more contaminants listed
in 179 NAC
2-002.04B2, then a
follow-up sample must be taken and analyzed within 14 days from each sampling
point included in the composite.
b.
If duplicates of the original sample taken from each sampling point used in the
composite are available, the system may use these instead of resampling. The
duplicates must be analyzed and the results reported to the Director within 14
days of collection.
c. If the
population served by the system is greater than 3,300 individuals, compositing
may only be permitted by the Director at sampling points within a single
system. In systems serving less than or equal to 3,300 individuals, the
Director may permit compositing among different systems provided the 5-sample
limit is maintained.
11.
Compliance Calculations: Compliance with 179 NAC
2-002.04B2 must be
determined based on the analytical results obtained at each sampling point. If
one sampling point is in violation of an MCL, the system is in violation of the
MCL.
a. For systems monitoring more than once
per year, compliance with the MCL is determined by a running annual average of
all samples taken at each sampling point.
b. Systems monitoring annually or less
frequently whose sample result exceeds the regulatory detection level as
defined by 179 NAC 3-007 item 17 must begin quarterly sampling. The system will
not be considered in violation of the MCL until it has completed one year of
quarterly sampling.
c. If any
sample result will cause the running annual average to exceed the MCL at any
sampling point, the system is out of compliance with the MCL
immediately.
d. If a system fails
to collect the required number of samples, compliance will be based on the
total number of samples collected.
e. If a sample result is less than the
detection limit, zero will be used to calculate the annual average.
12.
PCB
Analysis: Analysis for PCBs must be conducted as follows using the
methods in
40 CFR
141.24(e).:
a. Each system owner who monitors for PCBs
must analyze each sample using either Method 508.1, 525.2, 508 or 505. (Note:
Users of Method 505 may have more difficulty in achieving the required Aroclor
detection limits than users of Methods 508.1, 525.2 or 508.)
b. If PCBs (as one of seven Aroclors) are
detected (as designated in 179 NAC 3-007.03 item 12.b.) in any sample analyzed
using Methods 505 or 508, the system must reanalyze the sample using Method
508A to quantitate PCBs (as decachlorobiphenyl).
Aroclor
|
Detection Limit
(mg/L)
|
1016
|
0.00008
|
1221
|
0.02
|
1232
|
0.0005
|
1242
|
0.0003
|
1248
|
0.0001
|
1254
|
0.0001
|
1260
|
0.0002
|
c.
Compliance with the PCB MCL will be determined based upon the quantitative
results of analyses using Method 508A.
13.
Grandfathered
Data: If monitoring data collected after January 1, 1990, are
generally consistent with the requirements of 179 NAC 3-007.03, then the
Director will allow owners of systems to use that data to satisfy the
monitoring requirement for the initial compliance period.
14.
Increased
Sampling: The Director may increase the required monitoring
frequency, where necessary, to detect variations within the system (e.g.,
fluctuations in concentration due to seasonal use, changes in water
source).
15.
State
Enforcement: The Director has the authority to determine
compliance or initiate enforcement action based upon analytical results and
other information compiled by its sanctioned representatives and
agencies.
16.
Designated Sampling Schedules: Each public water
system owner must monitor at the time designated by the Director within each
compliance period.
17.
Detection Limits: Detection as used in 179 NAC
3-007.03 item 17 is defined as greater than or equal to the following
concentrations for each contaminant.
Contaminant
|
Detection Limit
(mg/L)
|
Alachlor
|
0.0002
|
Aldicarb
|
0.0005
|
Aldicarb sulfoxide
|
0.0005
|
Aldicarb sulfone
|
0.0008
|
Atrazine
|
0.0001
|
Benzo[a]pyrene
|
0.00002
|
Carbofuran
|
0.0009
|
Chlordane
|
0.0002
|
Dalapon
|
0.001
|
1,2-Dibromo-3-chloropropane (DBCP)
|
0.00002
|
Di(2-ethylhexyl)adipate
|
0.0006
|
Di(2-ethylhexyl)phthalate
|
0.0006
|
Dinoseb
|
0.0002
|
Diquat
|
0.0004
|
2,4-D
|
0.0001
|
Endothall
|
0.009
|
Endrin
|
0.00001
|
Ethylene dibromide (EDB)
|
0.00001
|
Glyphosate
|
0.006
|
Heptachlor
|
0.00004
|
Heptachlor epoxide
|
0.00002
|
Hexachlorobenzene
|
0.0001
|
Hexachlorocyclopentadiene
|
0.0001
|
Lindane
|
0.00002
|
Methoxychlor
|
0.0001
|
Oxamyl
|
0.002
|
Picloram
|
0.0001
|
Polychlorinated biphenyls
|
(PCBs) (as decachlorobiphenyl)
|
0.0001
|
Pentachlorophenol
|
0.00004
|
Simazine
|
0.00007
|
Toxaphene
|
0.001
|
2,3,7,8-TCDD (Dioxin)
|
0.000000005
|
2,4,5-TP (Silvex)
|
0.0002
|
18.
Laboratory Certification: Analysis under 179 NAC
3-006 must only be conducted by the
Public Health Environmental Laboratory or other laboratories approved by the
Director and certified by EPA or the Director. To receive certification to
conduct analyses for the contaminants in 179 NAC
2-002.04B2 the
laboratory must:
a. Analyze Performance
Evaluation samples which include those substances provided by EPA Environmental
Monitoring and Support Laboratory or equivalent samples provided by the
Director at least once a year by each method for which the laboratory desires
certification.
b. For each
contaminant that has been included in the PE sample achieve quantitative
results on the analyses that are within the following acceptance limits:
Contaminant
|
Acceptance Limits
(%)
|
Alachlor
|
± 45.
|
Aldicarb
|
2 standard deviations
|
Aldicarb sulfoxide
|
2 standard deviations
|
Aldicarb sulfone
|
2 standard deviations
|
Atrazine
|
± 45.
|
Benzo[a]pyrene
|
2 standard deviations
|
Carbofuran
|
± 45.
|
Chlordane
|
± 45.
|
Dalapon
|
2 standard deviations
|
DBCP
|
± 40.
|
Di(2-ethylhexyl)adipate
|
2 standard deviations
|
Di(2-ethylhexyl)phthalate
|
2 standard deviations
|
Dinoseb
|
2 standard deviations
|
Diquat
|
2 standard deviations
|
EDB
|
± 40.
|
Endothall
|
2 standard deviations
|
Endrin
|
± 30.
|
Glyphosate
|
2 standard deviations
|
Heptachlor
|
± 45.
|
Heptachlor epoxide
|
± 45.
|
Hexachlorobenzene
|
2 standard deviations
|
Hexachlorocyclopentadiene
|
2 standard deviations
|
Lindane
|
± 45.
|
Methoxychlor
|
± 45.
|
Oxamyl
|
2 standard deviations
|
PCBs (as decachlorobiphenyl)
|
0-200.
|
Pentachlorophenol
|
± 50.
|
Picloram
|
2 standard deviations
|
Simazine
|
2 standard deviations
|
Toxaphene
|
± 45.
|
2,3,7,8-TCDD (Dioxin)
|
2 standard deviations
|
2,4-D
|
± 50.
|
2,4,5-TP (Silvex)
|
± 50.
|
19. All new systems or systems that use a new
source of water that begin operation after January 22, 2004 must demonstrate
compliance with the MCL within a period of time specified by the Director. The
system must also comply with the initial sampling frequencies specified by the
Director to ensure a system can demonstrate compliance with the MCL. Routine
and increased monitoring frequencies must be conducted in accordance with the
requirements in 179 NAC 3-007.