Nebraska Administrative Code
Topic - HEALTH AND HUMAN SERVICES SYSTEM
Title 179 - PUBLIC WATER SYSTEMS
Chapter 25 - LONG TERM 2 (LT2) ENHANCED SURFACE WATER TREATMENT
Section 179-25-020 - TREATMENT PERFORMANCE TOOLBOX COMPONENTS
Current through September 17, 2024
020.01 Combined Filter Performance
Systems using conventional filtration treatment or direct filtration treatment receive an additional 0.5-log Cryptosporidium treatment credit during any month the system meets the criteria in this paragraph. Combined filter effluent (CFE) turbidity must be less than or equal to 0.15 NTU in at least 95% of the measurements. Turbidity must be measured as described in 179 NAC 13-007.01 and 13-007.03.
020.02 Individual Filter Performance
Systems using conventional filtration treatment or direct filtration treatment receive 0.5-log Cryptosporidium treatment credit, which can be in addition to the 0.5-log credit under 179 NAC 25-020.01, during any month the system meets the criteria in this paragraph. Compliance with these criteria must be based on individual filter turbidity monitoring as described in 179 NAC 17-006 or 19-010, as applicable.
020.03 Demonstration of Performance
The Department may approve
Cryptosporidium treatment credit for drinking water treatment processes based on a demonstration of performance study that meets the criteria in this paragraph. This treatment credit may be greater than or less than the prescribed treatment credits in 179 NAC 25-013 or 25-019 through 25-022 and may be awarded to treatment processes that do not meet the criteria for the prescribed credits.