Nebraska Administrative Code
Topic - HEALTH AND HUMAN SERVICES SYSTEM
Title 179 - PUBLIC WATER SYSTEMS
Chapter 22 - OPERATION AND MAINTENANCE OF COMMUNITY AND NON-TRANSIENT NON-COMMUNITY PUBLIC WATER SYSTEMS
Section 179-22-007 - DISTRIBUTION SYSTEMS

Current through March 20, 2024

All community and NTNC public water systems must:

1. Operate to maintain a minimum positive pressure of 20 psi throughout the distribution system except under extraordinary conditions such as unusual peak fire flow demand or major distribution system breaks.

2. Maintain an up-to-date map of the distribution system showing locations, sizes and materials of underground lines and appurtenances.

3. Following a drop in system pressure to less than 20 psi, but maintaining a positive pressure, collect a minimum of two water samples at least 24 hours apart from each affected zone on the sample site plan. All samples must be collected within five working days of the recorded drop in system pressure and submitted for analysis to the Department Laboratory or to a laboratory that has entered into an agreement with the Department pursuant to 179 NAC 3-009. If any samples collected pursuant to the requirements of 179 NAC 22-006 item 3 show the presence of coliform organisms, disinfection procedures must be accomplished in accordance with AWWA Standard C 651-99. Alternate disinfection procedures may be used after consultation with and approval by the Director. If used, alternate disinfection procedures must continue until collection of water samples as prescribed in 179 NAC 22-006 item 3 show the complete absence of coliform organisms.

4. When system pressure is completely lost, collect a minimum of two sets of five samples from each affected zone on the sample site plan. Each set must be collected at least 24 hours apart. All samples must be collected within five working days of the recorded complete loss in system pressure and submitted for analysis to the Department Laboratory or a laboratory that has entered into an agreement with the Department pursuant to 179 NAC 3-009. If any samples collected pursuant to the requirements of 179 NAC 22-006 item 4 show the presence of coliform organisms, disinfection procedures must be accomplished in accordance with AWWA Standard C 651-99. Alternate disinfection procedures may be used after consultation with and approval by the Director. If used, emergency disinfection procedures must continue until collection of water samples as prescribed in 179 NAC 22-006 item 4 show the complete absence of coliform organisms.

Disclaimer: These regulations may not be the most recent version. Nebraska may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.