Nebraska Administrative Code
Topic - HEALTH AND HUMAN SERVICES SYSTEM
Title 179 - PUBLIC WATER SYSTEMS
Chapter 13 - SURFACE WATER TREATMENT
Section 179-13-007 - ANALYTICAL AND MONITORING REQUIREMENTS

Current through September 17, 2024

007.01 Analytical Requirements

Only the analytical method(s) specified in 179 NAC 13-007 can be used to demonstrate compliance with the requirements of 179 NAC 13-004, 13-005, and 13-006. Measurements for pH, temperature, turbidity, and residual disinfectant concentrations must be conducted by a Grade I, II, III, or IV operator or a person who has been trained to take the samples. Attachment 4 (which is hereby incorporated by reference), which states that the person taking the samples has been trained to take them, must be completed, dated, and signed by the person doing the training (a Grade I, II, III, or IV licensed water operator) as well as the person trained. That form must be sent to the Department. Measurements for total coliforms, fecal coliforms, and heterotrophic plate count (HPC) must be conducted by the Department Laboratory or an approved laboratory as required in 179 NAC 3-009. Until laboratory certification criteria are developed for the analysis of fecal coliforms and HPC, any laboratory certified for total coliforms analysis by the Department or EPA is deemed certified for fecal coliforms and HPC analysis.

13-007.01A Public water systems must conduct analysis of pH and temperature in accordance with one of the methods found in 179 NAC 3-005.11A. Public water systems must conduct analysis of total coliforms, fecal coliforms, heterotrophic bacteria, and turbidity in accordance with one of the analytical methods in 40 CFR 141.74(a)(1) or an equivalent method approved by EPA and by using analytical test procedures contained in Technical Notes on Drinking Water Methods, EPA-600/R- 94-173, October 1994, which is available at NTIS PB 95-104766.

13-007.01B Public water systems must measure residual disinfectant concentrations with one of the analytical methods in 40 CFR 141.74(a)(2) or an equivalent method approved by EPA.

007.02 Monitoring Requirements for Systems That Do Not Provide Filtration

A public water system that uses a ground water source under the direct influence of surface water and does not provide filtration treatment must begin monitoring as specified in 179 NAC 13 beginning six months after the Director determines that the ground water source is under the direct influence of surface water, unless filtration is required, in which case the Director may specify alternative monitoring requirements, as appropriate, until filtration is in place.

13-007.02A Fecal coliform or total coliform density measurements as required by 179 NAC 13-004.01A must be performed on representative source water samples immediately prior to the first or only point of disinfectant application. The owner of the system must sample for fecal or total coliforms at the following minimum frequency each week the system serves water to the public:

System size (individuals served)

Samples per week1

500 or less

1

501 to 3,300

2

3,301 to 10,000

3

10,001 to 25,000

4

Over 25,000

5

1Must be taken on separate days

Also, one fecal or total coliform density measurement must be made every day the system serves water to the public and the turbidity of the source water exceeds 1 NTU (these samples count toward the weekly coliform sampling requirement) unless the Director determines that the system, for logistical reasons outside the system's control, cannot have the sample analyzed within 30 hours of collection.

13-007.02B Turbidity measurements as required by 179 NAC 13-004.01B must be performed on representative grab samples of source water immediately prior to the first or only point of disinfectant application every four hours (or more frequently) that the system serves water to the public. A public water system owner may substitute continuous turbidity monitoring for grab sample monitoring if it validates the continuous measurement for accuracy on a regular basis.

13-007.02C The total inactivation ratio for each day that the system is in operation must be determined based on the CT( 99.9) values in Tables 13.1 through 13.8 of 179 NAC 13-007. The parameters necessary to determine the total inactivation ratio must be monitored as follows:

*These CT values achieve greater than a 99.99% inactivation of viruses. CT values between the indicated pH values may be determined by linear interpolation. CT values between the indicated temperatures of different tables may be determined by linear interpolation. If no interpolation is used, use the CT( 99.9) value at the lower temperature and at the higher pH.

TABLE 13.2

CT VALUES [CT( 99.9)] for 99.9% INACTIVATION OF GIARDIA LAMBLIA CYSTS BY FREE CHLORINE AT 5.0°C *

pH

Residual mg/l

<6.0

6.5

7.0

7.5

8.0

8.5

<9.0

< 0.4

97

117

139

166

198

236

279

0.6

100

120

143

171

204

244

291

0.8

103

122

146

175

210

252

301

1.0

105

125

149

179

216

260

312

1.2

107

127

152

183

221

267

320

1.4

109

130

155

187

227

274

329

1.6

111

132

158

192

232

281

337

1.8

114

135

162

196

238

287

345

2.0

116

138

165

200

243

294

353

2.2

118

140

169

204

248

300

361

2.4

120

143

172

209

253

306

368

2.6

122

146

175

213

258

312

375

2.8

124

148

178

217

263

318

382

3.0

126

151

182

221

268

324

389

*These CT values achieve greater than a 99.99% inactivation of viruses. CT values between the indicated pH values may be determined by linear interpolation. CT values between the indicated temperatures of different tables may be determined by linear interpolation. If no interpolation is used, use the CT( 99.9) value at the lower temperature and at the higher pH.

TABLE 13.3

CT VALUES [CT( 99.9)] for 99.9% INACTIVATION OF GIARDIA LAMBLIA CYSTS BY FREE CHLORINE AT 10.0°C *

pH

Residual mg/l

<6.0

6.5

7.0

7.5

8.0

8.5

<9.0

<0.4

73

88

104

125

149

177

209

0.6

75

90

107

128

153

183

218

0.8

78

92

110

131

158

189

226

1.0

79

94

112

134

162

195

234

1.2

80

95

114

137

166

200

240

1.4

82

98

116

140

170

206

247

1.6

83

99

119

144

174

211

253

1.8

86

101

122

147

179

215

259

2.0

87

104

124

150

182

221

265

2.2

89

105

127

153

186

225

271

2.4

90

107

129

157

190

230

276

2.6

92

110

131

160

194

234

281

2.8

93

111

134

163

197

239

287

3.0

95

113

137

166

201

243

292

*These CT values achieve greater than a 99.99% inactivation of viruses. CT values between the indicated pH values may be determined by linear interpolation. CT values between the indicated temperatures of different tables may be determined by linear interpolation. If no interpolation is used, use the CT( 99.9) value at the lower temperature and at the higher pH.

TABLE 13.4

CT VALUES [CT( 99.9)] for 99.9% INACTIVATION OF GIARDIA LAMBLIA CYSTS BY FREE CHLORINE AT 15.0°C *

pH

Residual mg/l

<6.0

6.5

7.0

7.5

8.0

8.5

<9.0

<0.4

49

59

70

83

99

118

140

0.6

50

60

72

86

102

122

146

0.8

52

61

73

88

105

126

151

1.0

53

63

75

90

108

130

156

1.2

54

64

76

92

111

134

160

1.4

55

65

78

94

114

137

165

1.6

56

66

79

96

116

141

169

1.8

57

68

81

98

119

144

173

2.0

58

69

83

100

122

147

177

2.2

59

70

85

102

124

150

181

2.4

60

72

86

105

127

153

184

2.6

61

73

88

107

129

156

188

2.8

62

74

89

109

132

159

191

3.0

63

76

91

111

134

162

195

*These CT values achieve greater than a 99.99% inactivation of viruses. CT values between the indicated pH values may be determined by linear interpolation. CT values between the indicated temperatures of different tables may be determined by linear interpolation. If no interpolation is used, use the CT( 99.9) value at the lower temperature and at the higher pH.

TABLE 13.5

CT VALUES [CT( 99.9)] for 99.9% INACTIVATION OF GIARDIA LAMBLIA CYSTS BY FREE CHLORINE AT 20.0°C *

pH

Residual mg/l

<6.0

6.5

7.0

7.5

8.0

8.5

<9.0

<0.4

36

44

52

62

74

89

105

0.6

38

45

54

64

77

92

109

0.8

39

46

55

66

79

95

113

1.0

39

47

56

67

81

98

117

1.2

40

48

57

69

83

100

120

1.4

41

49

58

70

85

103

123

1.6

42

50

59

72

87

105

126

1.8

43

51

61

74

89

108

129

2.0

44

52

62

75

91

110

132

2.2

44

53

63

77

93

113

135

2.4

45

54

65

78

95

115

138

2.6

46

55

66

80

97

117

141

2.8

47

56

67

81

99

119

143

3.0

47

57

68

83

101

122

146

*These CT values achieve greater than a 99.99% inactivation of viruses. CT values between the indicated pH values may be determined by linear interpolation. CT values between the indicated temperatures of different tables may be determined by linear interpolation. If no interpolation is used, use the CT( 99.9) value at the lower temperature and at the higher pH.

TABLE 13.6

CT VALUES [CT( 99.9)] for 99.9% INACTIVATION OF GIARDIA LAMBLIA CYSTS BY FREE CHLORINE AT 25.0°C AND HIGHER*

pH

Residual mg/l

<6.0

6.5

7.0

7.5

8.0

8.5

<9.0

<0.4

24

29

35

42

50

59

70

0.6

25

30

36

43

51

61

73

0.8

26

31

37

44

53

63

75

1.0

26

31

37

45

54

65

78

1.2

27

32

38

46

55

67

80

1.4

27

33

39

47

57

69

82

1.6

28

33

40

48

58

70

84

1.8

29

34

41

49

60

72

86

2.0

29

35

41

50

61

74

88

2.2

30

35

42

51

62

75

90

2.4

30

36

43

52

63

77

92

2.6

31

37

44

53

65

78

94

2.8

31

37

45

54

66

80

96

3.0

32

38

46

55

67

81

97

*These CT values achieve greater than a 99.99% inactivation of viruses. CT values between the indicated pH values may be determined by linear interpolation. CT values between the indicated temperatures of different tables may be determined by linear interpolation. If no interpolation is used, use the CT( 99.9) value at the lower temperature and at the higher pH.

TABLE 13.7

CT VALUES [CT( 99.9)] for 99.9% INACTIVATION OF GIARDIA LAMBLIA CYSTS BY CHLORINE DIOXIDE AND OZONE*

Temperature

<1°C

5°C

10°C

15°C

20°C

25°C

Chlorine dioxide

63

26

23

19

15

11

Ozone

2.9

1.9

1.4

0.95

0.72

0.48

*These CT values achieve greater than a 99.99% inactivation of viruses. CT values between the indicated temperatures of different tables may be determined by linear interpolation. If no interpolation is used, use the CT( 99.9) value at the lower temperature and at the higher pH.

TABLE 13.8

CT VALUES [CT( 99.9)] for 99.9% INACTIVATION OF GIARDIA LAMBLIA CYSTS BY CHLORAMINES*

Temperature

<1°C

5°C

10°C

15°C

20°C

25°C

Chloramine

3,800

2,200

1,850

1,500

1,100

750

*These values are for pH values of 6 to 9. These CT values may be assumed to achieve greater than 99.99% inactivation of viruses only if chlorine is added and mixed in the water prior to the addition of ammonia. If this condition is not met, the system must demonstrate, in accordance with 179 NAC 13-006, that the system is achieving at least 99.99% inactivation of viruses. CT values between the indicated temperatures may be determined by linear interpolation. If no interpolation is used, use the CT( 99.9) value at the lower temperature for determining CT( 99.9) values between indicated temperatures.

13-007.02C1 The temperature of the disinfected water must be measured at least once per day at each residual disinfectant concentration sampling point.

13-007.02C2 If the system uses chlorine, the pH of the disinfected water must be measured at least once per day at each chlorine residual disinfectant concentration sampling point.

13-007.02C3 The disinfectant contact time(s) ("T") must be determined for each day during peak hourly flow.

13-007.02C4 The residual disinfectant concentration(s) ("C") of the water before or at the first customer must be measured each day during peak hourly flow.

13-007.02C5 If a system uses a disinfectant other than chlorine, the system may demonstrate to the Director that CT( 99.9) values other than those specified in Tables 13.7 and 13.8 in 179 NAC 13-007 or other operational parameters are adequate to demonstrate that the system is achieving the minimum inactivation rates required by 179 NAC 13-005.

TABLE 13.1

CT VALUES [CT( 99.9)] for 99.9% INACTIVATION OF GIARDIA LAMBLIA CYSTS BY FREE CHLORINE AT 0.5°C OR LOWER*

pH

Residual mg/l

<6.0

6.5

7.0

7.5

8.0

8.5

<9.0

<0.4

137

163

195

237

277

329

390

0.6

141

168

200

239

286

342

407

0.8

145

172

205

246

295

354

422

1.0

148

176

210

253

304

365

437

1.2

152

180

215

259

313

376

451

1.4

155

184

221

266

321

387

464

1.6

157

189

226

273

329

397

477

1.8

162

193

231

279

338

407

489

2.0

165

197

236

286

346

417

500

2.2

169

201

242

297

353

426

511

2.4

172

205

247

298

361

435

522

2.6

175

209

252

304

368

444

533

2.8

178

213

257

310

375

452

543

3.0

181

217

261

316

382

460

552

13-007.02D The total inactivation ratio must be calculated as follows:
13-007.02D1 If the system uses only one point of disinfectant application, the system owner may determine the total inactivation ratio based on either of the following two methods:
1. One inactivation ratio [CTcalc divided by CT( 99.9)] is determined before or at the first customer during peak hourly flow and if CTcalc divided by CT( 99.9) is greater than or equal to 1.0, the 99.9% Giardia lamblia inactivation requirement has been achieved; or

2. Successive CTcalc divided by CT( 99.9) values, representing sequential inactivation ratios, are determined between the point of disinfectant application and a point before or at the first customer during peak hourly flow. Under this alternative, the following method must be used to calculate the total inactivation ratio:
a. Determine CTcalc divided by CT( 99.9) for each sequence;

b. Add the CTcalc divided by CT( 99.9) values together; and

c. If the sum of CTcalc divided by CT( 99.9) is greater than or equal to 1.0, the 99.9% Giardia lamblia inactivation requirement has been achieved.

13-007.02D2 If the system used more than one point of disinfectant application before or at the first customer, the system owner must determine the CT value of each disinfection sequence immediately prior to the next point of disinfectant application during peak hourly flow. The CTcalc divided by CT( 99.9) value of each sequence and the sum of CTcalc divided by CT( 99.9) must be calculated using the method in 179 NAC 13-007.02D1 item 2 to determine if the system is in compliance with 179 NAC 13-005.01.

13-007.02D3 Although not required, the total percent inactivation for a system with one or more points of residual disinfectant concentration monitoring may be calculated by solving the following equation:

Percent inactivation = 100 - 100 divided by 10Z

Where: Z = 3 times the sum of CTcalc divided by CT( 99.9)

13-007.02E The residual disinfectant concentration of the water entering the distribution system must be monitored continuously, and the lowest value must be recorded each day, except that if there is a failure in the continuous monitoring equipment, grab sampling every four hours may be conducted in lieu of continuous monitoring, but for no more than five working days following the failure of the equipment. Owners of systems serving 3,300 or fewer individuals may take grab samples in lieu of providing continuous monitoring on an ongoing basis at the frequencies prescribed below:

System size by population

Samples per day1

500 or less

1

501 to 1,000

2

1,001 to 2,500

3

2,501 to 3,300

4

1The day's samples cannot be taken at the same time. The sampling intervals are subject to review and approval by the Director.

If at any time the residual disinfectant concentration falls below 0.2 mg per liter in a system using grab sampling in lieu of continuous monitoring, the system must take a grab sample every four hours until the residual concentration is equal to or greater than 0.2 mg per liter.

13-007.02F Measurement of Residual Disinfectant
13-007.02F1 Through March 31, 2016, the residual disinfectant concentration must be measured at least at the same points in the distribution system and at the same time as total coliforms are sampled, as specified in 179 NAC 3-004. Beginning April 1, 2016, the residual disinfectant concentration must be measured at least at the same points in the distribution system and at the same time as total coliforms are sampled, as specified in 179 NAC 26-006 through 26-010. The Director may allow a public water system which uses both a surface water source or a ground water source under the direct influence of surface water, and a ground water source to take disinfectant residual samples at points other than the total coliform sampling points if the Director determines that such points are more representative of treated (disinfected) water quality within the distribution system. Heterotrophic bacteria measured as heterotrophic plate count (HPC) as specified in 179 NAC 13-007.01A may be measured in lieu of residual disinfectant concentration.

13-007.02F2 If the Director determines, based on site-specific considerations, that a system has no means for having a sample transported and analyzed for HPC by an approved laboratory under the requisite time and temperature conditions required of the approved laboratory, and that the system is providing adequate disinfection in the distribution system, the requirements of 179 NAC 13-007.02F1 do not apply to that system.

007.03 Monitoring Requirements for Systems Using Filtration Treatment

A public water system that uses a surface water source or a ground water source under the influence of surface water and provides filtration treatment must monitor in accordance with 179 NAC 13-007 beginning June 29, 1993, or when filtration is installed, whichever is later.

13-007.03A Turbidity measurements as required by 179 NAC 13-006 must be performed on representative samples of the system's filtered water every four hours (or more frequently) that the system serves water to the public. A public water system owner may substitute continuous turbidity monitoring for grab sample monitoring if the owner validates the continuous measurement for accuracy on a regular basis. For any systems using slow sand filtration or filtration treatment other than conventional treatment, direct filtration, or diatomaceous earth filtration, the Director may reduce the sampling frequency to once per day if the Director determines that less frequent monitoring is sufficient to indicate effective filtration performance. For systems serving 500 or fewer individuals, the Director may reduce the turbidity sampling frequency to once per day, regardless of the type of filtration treatment used, if the Director determines that less frequent monitoring is sufficient to indicate effective filtration performance.

13-007.03B The residual disinfectant concentration of the water entering the distribution system must be monitored continuously, and the lowest value must be recorded each day, except that if there is a failure in the continuous monitoring equipment, grab sampling every four hours may be conducted in lieu of continuous monitoring, but for no more than five working days following the failure of the equipment. Owners of systems serving 3,300 or fewer individuals may take grab samples in lieu of providing continuous monitoring on an ongoing basis at the frequencies each day prescribed below:

System size by population

Samples per day1

500 or less

1

501 to 1,000

2

1,001 to 2,500

3

2,501 to 3,300

4

1The day's samples cannot be taken at the same time. The sampling intervals are subject to review and approval by the Director.

If at any time the residual disinfectant concentration falls below 0.2 mg per liter in a system using grab sampling in lieu of continuous monitoring, the system must take a grab sample every four hours until the residual concentration is equal to or greater than 0.2 mg per liter.

13-007.03C Measurement of Residual Disinfectant: Through March 31, 2016, the residual disinfectant concentration must be measured at least at the same points in the distribution system and at the same time as total coliforms are sampled, as specified in 179 NAC 3-004.01B. Beginning April 1, 2016, the residual disinfectant concentration must be measured at least at the same points in the distribution system and at the same time as total coliforms are sampled, as specified in 179 NAC 26-006 through 26-010. The Director may allow a public water system which uses both a surface water source or a ground water source under the direct influence of surface water, and a ground water source to take disinfectant residual samples at points other than the total coliform sampling points if the Director determines that such points are more representative of treated (disinfected) water quality within the distribution system. Heterotrophic bacteria, measured as heterotrophic plate count (HPC) as specified in 179 NAC 13-007.01A may be measured in lieu of residual disinfectant concentration.

Disclaimer: These regulations may not be the most recent version. Nebraska may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.