Nebraska Administrative Code
Topic - HEALTH AND HUMAN SERVICES SYSTEM
Title 179 - PUBLIC WATER SYSTEMS
Chapter 13 - SURFACE WATER TREATMENT
Section 179-13-006 - FILTRATION

Current through September 17, 2024

A public water system that uses a surface water source must provide treatment consisting of both disinfection, as specified in 179 NAC 13-005.02 and filtration treatment which complies with the requirements of 179 NAC 13-006.01 to 13-006.04 by June 29, 1993. A public water system that uses a ground source which is under the direct influence of surface water and does not meet all the criteria in 179 NAC 13-004 for avoiding filtration, must provide treatment consisting of both disinfection, as specified in 179 NAC 13-005.02 and filtration which complies with the requirements of 179 NAC 13-006.01 to 13-006.04 within 18 months of the failure to meet any one of the criteria for avoiding filtration in 179 NAC 13-004. Failure to meet any requirement of 179 NAC 13-006 is a treatment technique violation.

006.01 Conventional Filtration Treatment or Direct Filtration

13-006.01A For systems using conventional filtration or direct filtration, the turbidity level of representative samples of a system's filtered water must be less than or equal to 0.5 NTU in at least 95% of the measurements taken each month, measured as specified in 179 NAC 13-007.01A and 13-007.03A, except that if the Director determines that the system is capable of achieving at least 99.9% removal and/or inactivation of Giardia lamblia cysts at some turbidity level higher than 0.5 NTU in at least 95% of the measurements taken each month, the Director may substitute this higher turbidity limit for that system. However, in no case may the Director approve a turbidity limit that allows more than 1 NTU in more than 5% of the samples taken each month, measured as specified in 179 NAC 13-007.01A and 13-007.03A.

13-006.01B The turbidity level of representative samples of a system's filtered water must at no time exceed 5 NTU, measured as specified in 179 NAC 13-007.01A and 13-007.03A.

13-006.01C Beginning January 1, 2002, systems serving at least 10,000 people must meet the turbidity requirements in 179 NAC 17-006.01.

13-006.01D Beginning January 14, 2005, systems serving fewer than 10,000 people must meet the turbidity requirements in 179 NAC 19-009.01 through 19-009.04.

006.02 Slow Sand Filtration

13-006.02A For systems using slow sand filtration, the turbidity level of representative samples of a system's filtered water must be less than or equal to 1 NTU in at least 95% of the measurements taken each month, measured as specified in 179 NAC 13-007.01A and 13-007.03A, except that if the Director determines there is no significant interference with disinfection at a higher turbidity level, the Director may substitute this higher turbidity limit for that system.

13-006.02B The turbidity level of representative samples of a system's filtered water must at no time exceed 5 NTU, measured as specified in 179 NAC 13-007.01A and 13-007.03A.

006.03 Diatomaceous Earth Filtration

13-006.03A For systems using diatomaceous earth filtration, the turbidity level of representative samples of a system's filtered water must be less than or equal to 1 NTU in at least 95% of the measurements taken each month, measured as specified in 179 NAC 13-007.01A and 13-007.03A.

13-006.03B The turbidity level of representative samples of a system's filtered water must at no time exceed 5 NTU, measured as specified in 179 NAC 13-007.01A to 13-007.03A.

006.04 Other Filtration Technologies

: A public water system may use a filtration technology not listed in 179 NAC 13-006.01 to 13-006.03 if it demonstrates to the Director using pilot plant studies or other means, that the alternative filtration technology, in combination with disinfection treatment that meets the requirements of 179 NAC 13-005.02, consistently achieves 99.9% removal and/or inactivation of Giardia lamblia cysts and 99.99% removal and/or inactivation of viruses. For a system that makes this demonstration, the requirements of 179 NAC 13-006.02 apply. Beginning January 1, 2002, systems serving at least 10,000 people must meet the requirements for other filtration technologies in 179 NAC 17-005.02. Beginning January 14, 2005, systems serving fewer than 10,000 people must meet the requirements for other filtration technologies in 179 NAC 19-009.01 through 19-009.04.

Disclaimer: These regulations may not be the most recent version. Nebraska may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.