Section 179-12-005 - DESCRIPTION OF CORROSION CONTROL TREATMENT REQUIREMENTS

Current through September 17, 2024

Each system must complete the corrosion control treatment requirements described below which are applicable to such system under 179 NAC 12-004.

005.01 System Recommendation Regarding Corrosion Control Treatment

Based upon the results of lead and copper tap monitoring and water quality parameter monitoring, small and medium-size water systems exceeding the lead or copper action level must recommend installation of one or more of the corrosion control treatments listed in 179 NAC 12-005.03A which the system believes constitutes optimal corrosion control for that system. The Director may require the system to conduct additional water quality parameter monitoring in accordance with 179 NAC 12-010.02 to assist the Director in reviewing the system's recommendation.

005.02 Director Decision to Require Studies of Corrosion Control Treatment (Applicable to Small and Medium-Size Systems)

The Director may require any small or medium-size system that exceeds the lead or copper action level to perform corrosion control studies under 179 NAC 12-005.03 to identify optimal corrosion control treatment for the system.

005.03 Performance of Corrosion Control Studies

12-005.03A Any public water system performing corrosion control studies must evaluate the effectiveness of each of the following treatments, and, if appropriate, combinations of the following treatments to identify the optimal corrosion control treatment for that system:
1. Alkalinity and pH adjustment;

2. Calcium hardness adjustment; and

3. The addition of a phosphate or silicate based corrosion inhibitor at a concentration sufficient to maintain an effective residual concentration in all test tap samples.

12-005.03B The water system must evaluate each of the corrosion control treatments using either pipe rig/loop tests, metal coupon tests, partial-system tests, or analyses based on documented analogous treatments with other systems of similar size, water chemistry and distribution system configuration.

12-005.03C The water system must measure the following water quality parameters in any tests conducted under 179 NAC 12-005.03C before and after evaluating the corrosion control treatments listed above:
1. Lead;

2. Copper;

3. pH;

4. Alkalinity;

5. Calcium;

6. Conductivity;

7. Orthophosphate (when an inhibitor containing a phosphate compound is used);

8. Silicate (when an inhibitor containing a silicate compound is used); and

9. Water temperature.

12-005.03D The water system must identify all chemical or physical constraints that limit or prohibit the use of a particular corrosion control treatment and document such constraints with at least one of the following:
1. Data and documentation showing that a particular corrosion control treatment has adversely affected other water treatment processes when used by another water system with comparable water quality characteristics; and/or

2. Data and documentation demonstrating that the water system has previously attempted to evaluate a particular corrosion control treatment and has found that the treatment is ineffective or adversely affects other water quality treatment processes.

12-005.03E The water system must evaluate the effect of the chemicals used for corrosion control treatment on other water quality treatment processes.

12-005.03F On the basis of an analysis of the data generated during each evaluation, the water system must recommend to the Director in writing the treatment option that the corrosion control studies indicate constitutes optimal corrosion control treatment for that system. The water system must provide a rationale for its recommendation along with all supporting documentation specified in 179 NAC 12-005.03A through 12-005.03E.

005.04 Designation of Optimal Corrosion Control Treatment by the Director

12-005.04A Based upon consideration of available information including, where applicable, studies performed under 179 NAC 12-005.03 and a system's recommended treatment alternative, the Director must either approve the corrosion control treatment option recommended by the system, or designate alternative corrosion control treatment(s) from among those listed in 179 NAC 12-005.03A. When designating optimal treatment the Director must consider the effects that additional corrosion control treatment will have on water quality parameters and on other water quality treatment processes.

12-005.04B The Director must notify the system of its decision on optimal corrosion control treatment in writing and explain the basis for this determination. If the Director requests additional information to aid its review, the water system must provide the information.

005.05 Installation of Optimal Corrosion Control

Each system must properly install and operate throughout its distribution system the optimal corrosion control treatment designated by the Director under 179 NAC 12-005.04.

005.06 Director Review of Treatment and Specification of Optimal Water Quality Control Parameters

The Director must evaluate the results of all lead and copper tap samples and water quality parameter samples submitted by the water system and determine whether the system has properly installed and operated the optimal corrosion control treatment designated by the Director in 179 NAC 12-005.04. Upon reviewing the results of tap water and water quality parameter monitoring by the system, both before and after the system installs optimal corrosion control treatment, the Director must designate:

1. A minimum value or a range of values for pH measured at each entry point to the distribution system;

2. A minimum pH value, measured in all tap samples. Such value must be equal to or greater than 7.0, unless the Director determines that meeting a pH level of 7.0 is not technologically feasible or is not necessary for the system to optimize corrosion control;

3. If a corrosion inhibitor is used, a minimum concentration or a range of concentrations for the inhibitor, measured at each entry point to the distribution system and in all tap samples, that the Director determines is necessary to form a passivating film on the interior walls of the pipes of the distribution system;

4. If alkalinity is adjusted as part of optimal corrosion control treatment, a minimum concentration or a range of concentrations for alkalinity, measured at each entry point to the distribution system and in all tap samples;

5. If calcium carbonate stabilization is used as part of corrosion control, a minimum concentration or a range of concentrations for calcium, measured in all tap samples.

The values for the applicable water quality control parameters listed above must be those that the Director determines to reflect optimal corrosion control treatment for the system. The Director may designate values for additional water quality control parameters determined by the Director to reflect optimal corrosion control for the system. The Director must notify the system in writing of these determinations and explain the basis for its decisions.

005.07 Continued Operation and Monitoring

All systems optimizing corrosion control must continue to operate and maintain optimal corrosion control treatment, including maintaining water quality parameter values at or above minimum values or within ranges designated by the Director under 179 NAC 12-005.06, in accordance with 179 NAC 12-005.07 for all samples collected under 179 NAC 12-010.04 through 12-010.06. Compliance with the requirements of 179 NAC 12-005.07 must be determined every six months, as specified under 179 NAC 12-010.04. A water system is out of compliance with the requirements of 179 NAC 12-005.07 for a six-month period if it has excursions for any Director-specified parameter on more than nine days during the period. An excursion occurs whenever the daily value for one or more of the water quality parameters measured at a sampling location is below the minimum value or outside the range designated by the Director. Daily values are calculated as follows. The Director has discretion to delete results of obvious sampling errors from this calculation.

1. On days when more than one measurement for the water quality parameter is collected at the sampling location, the daily value must be the average of all results collected during the day regardless of whether they are collected through continuous monitoring, grab sampling, or a combination of both.

2. On days when only one measurement for the water quality parameter is collected at the sampling location, the daily value must be the result of that measurement.

3. On days when no measurement is collected for the water quality parameter at the sampling location, the daily value must be the daily value calculated on the most recent day on which the water quality parameter was measured at the sample site.

005.08 Modification of Treatment Decisions Made by the Director

Upon its own initiative or in response to a request by a water system or other interested party, the Director may modify his/her determination of the optimal corrosion control treatment under 179 NAC 12-005.04 or optimal water quality control parameters under 179 NAC 12-005.06. A request for modification by a system or other interested party must be in writing, explain why the modification is appropriate, and provide supporting documentation. The Director may modify his/her determination where s/he concludes that such change is necessary to ensure that the system continues to optimize corrosion control treatment. A revised determination must be made in writing, set forth the new treatment requirements, explain the basis for the Director's decision, and provide an implementation schedule for completing the treatment modifications.

Disclaimer: These regulations may not be the most recent version. Nebraska may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.