Current through March 20, 2024
The Department may consider alternate designs that follow
generally accepted engineering guidelines and standards with submitted
engineering justification.
005.01
EXISTING POOLS. Swimming pools constructed or under
construction prior to the effective date of these regulations, which do not
fully comply with the design and construction requirements of these regulations
may be continued in use as long as the swimming pool meets the current
operating requirements in 178 NAC 2, poses no significant health or safety
risks as determined by the Department or Director, and is operated and
maintained as designed.
005.02
MAXIMUM SWIMMING POOL PATRON LOADING.
005.02(A)
AREA
LOADING.005.02(A)(i)
SHALLOW AREA. 15 square feet of pool water surface
area must be provided for each patron for those portions of the swimming pool 5
feet or less in depth. This also applies to spray parks without standing
water.
005.02(A)(ii)
DEEP AREA. 25 square feet of pool surface area must be
provided for each patron.
005.02(A)(iii)
DIVING OR SLIDE
AREA. Where a separate designated diving or slide area is
provided, and other swimmers are not allowed in this area, this area may be
excluded from the surface area used for computing patron load; however, 10
patrons must be included for each board, platform or slide.
005.02(A)(iv)
ADDITIONAL AREA
ALLOWANCE. Additional allowance will be made on the basis of 1
additional patron per each 50 square feet of pool deck in excess of the minimum
area of deck required, and 1 additional patron per each 100 square feet of
picnic and play area within the enclosure.
005.03
CONSTRUCTION
MATERIAL.
005.03(A)
MATERIALS. Swimming pools must be constructed of
materials which are inert, stable, non-toxic, and watertight. Sand or earth
bottoms are not permitted.
005.03(B)
FINISH.
Bottom and sides must be white or a light color, with a smooth and easily
cleanable surface. The finish surface of the bottom in shallow areas must be
slip-resistant.
005.04
DESIGN, DETAIL, AND STRUCTURAL STABILITY. All swimming
pools and appurtenances must be designed and constructed to withstand all
anticipated patron loading. A hydrostatic relief valve or a suitable underdrain
system must be provide for in-ground pools. Swimming pools must be designed to
ensure the stability of the pool for both full and empty conditions.
005.04(A)
SHAPE. The
shape of any swimming pool must be such that the circulation of pool water and
the swimmers' safety are not impaired. There may not be any underwater
projections or obstructions which would endanger patron safety or interfere
with proper pool operation.
005.04(B)
BOTTOM
SLOPE. The bottom of the pool must slope toward the main drain.
Where the water depth is less than 5 feet, the bottom slope must not exceed 1
foot vertical in 12 feet horizontal (1:12). Where the water depth exceeds 5
feet, the bottom slope must not exceed 1 foot vertical in 3 feet horizontal
(1:3).
005.04(C)
POOL
WALLS. Walls of a swimming pool must be either:
(i) Vertical for water depths of at least 6
feet;
(ii) Vertical for a distance
of at least 3 feet below the water level, below which the wall may be curved to
the bottom with a radius not greater than the difference between the depth at
that point and 3 feet, provided that the vertical is interpreted to permit
slopes not greater than 1 foot horizontally for each 5 feet of depth of
sidewall (11 degrees from vertical); or
(iii) At water depths of 3 feet or less a
transitional radius must not exceed 8 inches and must be tangent to the wall
and floor.
005.04(D)
LEDGES. Ledges must not extend into the pool unless
they are essential for support of the upper wall construction.
005.04(E)
POOLS WITHOUT
GUTTERS. Coping or cantilevered deck may project from a swimming
pool or spa wall to provide a handhold for users. The coping or deck must be
rounded, have a slip-resistant surface finish, and must not exceed 3-1/2 inches
in thickness. The overhang of the coping or deck must not exceed 2 inches or be
less than 1 inch. All corners created by coping or cantilevered deck must be
rounded in both the vertical and horizontal dimensions to eliminate sharp
corners. The handgrip must not be more than 9 inches above the minimum skimmer
operating level.
005.04(F)
DIVING AREAS. The minimum dimensions of the swimming
pool and appurtenances in the diving area must conform to 178 NAC 2 Table 1.
005.04(F)(i)
HEAD
ROOM. There must be a completely unobstructed clear distance of 16
feet above the diving board measured from the center of the front end of the
board. This area must extend at least 8 feet behind, 8 feet to each side, and
16 feet ahead of the measuring point.
005.04(F)(ii)
DIVING BOARDS AND
PLATFORMS. Diving boards and platforms in excess of 3 meters in
height are prohibited except where special design considerations and control of
use are provided.
005.04(F)(iii)
STEPS AND GUARD RAILS FOR DIVING BOARDS. Steps must be
of corrosion-resistant material, easily cleanable and of non-slip design.
Handrails must be provided at all steps and ladders leading to diving boards
more than 1 meter above the water. Platforms and diving boards which are more
than 1 meter high must be protected with guard rails at least 36 inches high,
extending at least to the edge of the water. Boards or platforms 3 meters ( 9.8
ft.) or higher, when permitted, must have an effective side barrier.
Click here
to view
TABLE 1
MINIMUM DIMENSIONS FOR POOLS WITH DIVING EQUIPMENT
| MINIMUM
DIMENSIONS |
Maximum Board Height Over Water | Maximum Diving
Board
Length | D | L1 | L2 | POOL
WIDTH |
26" (2/3 meter) | 10' | 8' - 6" | 2'
- 6" | 10' - 0" | 20' - 0" |
30" (3/4 meter) | 12' | 9' - 0" | 3'
- 0" | 10' - 0" | 20' - 0" |
1 meter | 16' | 10' - 0" | 4' -
0" | 12' - 0" | 20' - 0" |
3 meter | 16' | 12' - 0" | 6' -
0" | 12' - 0" | 24' - 0" |
005.04(F)(iv)
PLACEMENT. Placement of boards must observe the
following minimum dimensions. With multiple board installations minimum pool
widths must be increased accordingly. For diving boards or platforms greater
than 20 inches in width, add ½ of the width over 20 inches to the
following dimensions.
Center line of 1 meter or less board to pool side 10' -
0"
Center line of 3 meters board to pool side 12' - 0"
Center line distance between adjacent boards 10' -
0"
005.05
LADDERS, RECESSED STEPS,
AND STAIRS.
005.05(A)
LOCATION. Recessed steps, ladders, or stairs must be
provided at the shallow end. Ladders or recessed steps must be provided at the
deep end. If the pool is over 30 feet wide, the steps, ladders, or stairs must
be installed on each side.
005.05(B)
LADDERS.
Pool ladders must be corrosion-resistant and must have slip-resistant treads.
All ladders must be designed to provide a handhold. There must be a clearance
of not more than 6 inches or less than 3 inches between any ladder and pool
wall. Treads must be no more than 12 inches apart.
005.05(C)
RECESSED
STEPS. Recessed steps must be readily cleanable, slip-resistant,
and must be arranged to drain into the pool. Recessed steps must have a minimum
tread of 5 inches and a minimum width of 14 inches. Steps must be no more than
12 inches apart.
005.05(D)
HANDRAILS. Where recessed steps or ladders are
provided, there must be a handrail at the top of each side thereof, extending
over the coping or edge of the deck.
005.05(E)
STAIRS AND STAIR
HANDRAILS. Where stairs are provided, they must be located in a
corner of the pool or be recessed. All stair areas must have a handrail within
reach. Stairs must have slip-resistant finish, a minimum tread of 12 inches,
and a maximum rise of 12 inches.
005.06
UNDERWATER BENCHES AND SUN
LEDGES.
005.06(A)
UNDERWATER BENCHES. Requirements for underwater
benches are as follows:
(i) Must be slip
resistant;
(ii) The horizontal
surface must be a maximum of 20 inches below water line;
(iii) An unobstructed surface must be
provided that is 12 to 18 inches deep and a minimum of 24 inches wide;
(iv) Jets are not allowed in
conjunction with benches;
(v) May
be installed in varying depths, but the maximum water depth will not exceed 5
feet; and underwater seats may be located in deep areas of the pool where
diving equipment, either manufactured or constructed, is installed, provided
they are located outside of the minimum water envelope for diving equipment;
and
(vi) Vertical and horizontal
leading edges must be visually set apart with a continuous slip-resistant
marking not less than 2/3 inch and not greater than 2 inches.
005.06(B)
SUN LEDGES AND UNDERWATER SHELVES. The requirements
for sun ledges and underwater shelves are as follows:
(i) Depth must be 12 inches or
less;
(ii) The area leading to the
deep portion of the pool must have stairs with handrails within
reach;
(iii) The horizontal leading
edge of each stair will be visually set apart;
(iv) There must be depth markers at the top
and bottom of the stairs;
(v) The
sun ledge slope not to exceed 1:12; and
(vi) There must be a minimum of two bottom
inlets.
005.07
DECKS. A
portion of the deck from the edge of the pool at least 5 feet wide must be
unobstructed unless approved in the construction permit or a variance is
obtained. The deck must be of a uniform, easily cleaned, impervious material
with a slip-resistant finish. Wood decks are expressly prohibited within 5 feet
of the pool. The deck must be protected from surface runoff.
005.07(A)
SLOPE. The
deck must be sloped away from the pool unless drains are provided to intercept
water on the way back to the pool, and must be sloped to provide positive
drainage of all deck areas.
005.07(B)
DRAINAGE.
Deck drains, when used, must be no more than 25 feet apart, and no single drain
can serve more than 400 square feet of area. Continuous trench-style drains may
be designed to handle areas greater than 400 square feet. There must be no
direct connection between the pool deck drains and the storm or sanitary sewer
or plumbing drainage systems unless approved in the construction permit or a
variance is obtained. They must not drain to the pool gutter or recirculation
systems.
005.07(C)
ROLL-OUT GUTTERS. If the pool is equipped with
roll-out, deck-level gutters, not more than 5 feet of deck may be sloped toward
the gutters.
005.07(D)
CARPETING. Carpeting is not permitted on pool decks.
005.07(E)
HOSE
BIBS. At least 1 hose bib with an appropriate backflow preventer
must be provided to facilitate cleaning the deck areas.
005.07(F)
POOL
CONCESSIONS. Where concessions are provided, an area or areas
separate from the pool deck must be designated for serving and consuming food
or drink.
005.07(G)
DRINKING FOUNTAIN. A minimum of 1 drinking fountain
must be located in the swimming pool area for Class A swimming pools. Each
drinking fountain must be connected to a water system that meets the
requirements of 178 NAC
2-005.10(A).
005.08BARRIERS. The
pool area must be completely surrounded by an effective barrier not less than 6
feet high. Any special purpose areas inside the barrier must be fenced or
constructed to control traffic. These areas must be designed so they will not
drain onto the deck. Any entrance to the pool area must be provided with a
self-closing and latching gate or door capable of being locked unless another
means of controlling access is provided. The operating controls for the
self-latching device must be located at least 48" above the exterior ground
surface or pool deck. Barrier openings must be small enough that a 4-inch
sphere is not able to pass through.
005.09LIGHTING, ELECTRICAL, AND
VENTILATION REQUIREMENTS.
005.09(A)
LIGHTING.
During periods of operation sufficient illumination must be provided to allow
visibility of all portions of the pools, including the bottom. Illumination
must be provided by natural or artificial means by the following:
(i) Overhead lighting must provide a minimum
of 3 foot candles of illumination at the pool water surface and the adjacent
deck area;
(ii) Underwater lighting
must provide a minimum of 0.5 watts per square foot of pool water surface; and
(iii) Underwater lighting
requirements may be approved when the overhead lighting provides a minimum of
15 foot candles of illumination at the pool water surface.
005.09(B)
ELECTRICAL. All electrical installations must conform
to the requirements of the State Electrical Act, Neb. Rev. Stat. §§
81-2101
through
81-2143.
005.09(C)
HEATING AND
VENTILATION. Indoor bathhouses, mechanical equipment rooms,
storage areas, and pool enclosures must be heated and ventilated. Room
ventilation must prevent direct drafts on swimmers and must minimize
condensation damage. A fuel-burning heating unit must be provided with air for
combustion and vented to the outdoors.
005.10
WATER SUPPLY AND WASTE
WATER DISPOSAL.
005.10(A)
WATER SUPPLY. Water supplied to a swimming pool and
all related plumbing fixtures must use water from a public water system (PWS)
or if a public water system (PWS) is not available, water quality must meet the
requirements for coliform bacteria and nitrates that apply to a transient
public water system in accordance with Title 179.
005.10(B)
CROSS-CONNECTION
CONTROL. All portions of the water distribution system serving a
public swimming pool and related facilities must be protected against backflow
and back siphonage. Water introduced into the pool, either directly or to the
recirculation system, must be through an air gap or an appropriate approved
backflow preventer as required by the Department.
005.10(C)
SANITARY
WASTES. Disposal must follow Title 123 or 124. Where available, a
municipal sanitary sewage system must be used.
005.10(D)
BACKFLOW
PREVENTION. In a swimming pool, the recirculation system and pool
deck drains must be protected against the backflow of waste water in a manner
approved by the Department.
005.10(E)
CONDENSATE. Condensate must not be introduced to the
pool water or any part of the recirculation system.
005.10(F)
HEAT
EXCHANGERS. Any heating, dehumidification or cooling system which
is connected in any way with the pool recirculation system must contain only
nontoxic heat transfer media.
005.11
RECIRCULATION
SYSTEM. Each swimming pool must be provided with a separate
recirculation system, which will convey, clarify, chemically balance and
disinfect the swimming pool water.
005.11(A)
COMPONENTS. Recirculation system components must be
certified to American National Standards Institute/National Sanitation
Foundation (ANSI/NSF) Standard 50 by an organization accredited by the American
National Standards Institute.
005.11(B)
RECIRCULATION
RATE. A swimming pool recirculation system must meet volume and
rate of exchange in Table 2.
Pool Turnover Rate Table 2
Type or Depth of Pool
|
Required Turnover Rate
|
Spray parks with no standing water
|
1 system volume of water every 30 minutes or less
for a water treatment tank
|
Pool areas less than or equal to 2 feet in water
depth
|
1 pool volume of water every 1 hour or less
|
Pool areas greater than 2 feet but less than or
equal to 3 feet in water depth
|
1 pool volume of water every 2 hours or less
|
Pool areas greater than 3 feet but less than or
equal to 5 feet in water depth
|
1 pool volume of water every 4 hours or less
|
Pool areas greater than 5 feet in water
depth
|
1 pool volume of water every 6 hours or less
|
Plunge Pool for Flume Slide
|
1 pool volume of water every 1 hour or less
|
005.11(C)
MATERIALS.
Recirculation system components in contact with the swimming pool water must be
of non-toxic material, resistant to corrosion, suitable for potable water use,
and able to withstand operating pressures.
005.11(D)
PIPE
SIZING. Recirculation piping must be designed so that the water
velocity does not exceed 10 feet per second on the discharge side of the
recirculation pump, and 6 feet per second in suction piping. Gravity piping
must be sized in accordance with accepted engineering practice with
consideration of available head.
005.11(E)
DRAINAGE AND
INSTALLATION. All equipment and piping must be designed and
fabricated to drain completely by use of drain plugs, drain valves or other
means. All piping must be supported to prevent sagging. All suction piping must
be sloped in 1 direction.
005.11(F)
PIPE VALVE AND IDENTIFICATION. All exposed piping must
be clearly marked to indicate function and use.
005.11(G)
OVERFLOW
SYSTEMS. All pools must be designed to provide continuous
skimming. Makeup water supply equipment must be provided to maintain continuous
skimming.
005.11(G)(i)
GUTTERS
(PERIMETER OVERFLOW SYSTEMS). The gutter must extend around the
full perimeter of the swimming pool except at stairways and ramps 6 feet or
less in width entering the swimming pool. It must be level within a tolerance
of plus or minus 1/8 inch. Piping connections must be provided to permit water
to flow from overflows to the recirculation system.
005.11(G)(i)(1)
SIZE AND
SHAPE. The gutter system must be designed to allow continuous
removal of water from the pool's upper surface at a rate of at least 125
percent of the recirculation rate. The gutter must be designed to serve as a
handgrip and to prevent entrapment of arms or legs.
005.11(G)(i)(2)
OUTLETS. Drop boxes, converters, return piping or
flumes used to convey water from the gutter must be designed to handle at least
125 percent of the recirculation rate. Drainage must be sufficient to minimize
flooding and prevent backflow of skimmed water into the pool.
005.11(G)(i)(3)
SURGE
CAPACITY. All overflow systems must be designed with an effective
surge capacity of not less than 1 gallon for each square foot of pool surface
area. Surge must be provided within a surge tank, in the gutter or filter above
the normal flow line, or elsewhere in the system. Surge tanks, gutters, and
filter tanks must have overflow pipes to convey excess water to waste. Surge
tanks must be provided with means for complete draining. In-pool surge is
allowed only with an engineered perimeter gutter system which includes an
integral surge weir for each 500 square feet of water surface, and a tank to
allow balancing of main drain and gutter flows.
005.11(G)(ii)
SKIMMERS. The use of skimmers is limited to pools with
widths of 30 feet or less.
005.11(G)(ii)(1)
CONSTRUCTION. Skimmers must be installed in the pool
walls, and be constructed of corrosion-resistant materials. Skimmers must bear
the American National Standards Institute/National Sanitation Foundation
(ANSI/NSF) 50 certification mark or be certified to ANSI/NSF Standard 50 by an
organization accredited by the American National Standards Institute.
005.11(G)(ii)(2)
NUMBER. At least 1 surface skimmer must be provided
for each 500 square feet of surface or fraction thereof. At least 2 skimmers
must be provided.
005.11(G)(ii)(3)
LOCATION. Skimmers must be located as to provide
effective skimming of the entire water surface with minimum interference and
short-circuiting.
005.11(G)(ii)(4)
FLOW RATE. Skimmers must provide for a flow-through
rate of 30 gallons per minute or 3.75 gallons per minute per lineal inch of
weir, whichever is greater.Skimmer piping must be designed to handle a minimum
of 100% of the pool turnover rate.
005.11(G)(ii)(5)
CONTROL. Skimmers must have weirs that adjust
automatically and operate freely and continuously with variations of at least 4
inches in water level. All skimmed water must pass through an easily removable
and cleanable basket or screen before encountering control valves or entering
the pump suction line. Each skimmer must be equipped with a device to control
flow. If a skimmer is connected directly to the recirculation pump suction
pipe, it must include a device to prevent an airlock in the suction line. If
equalizer pipes are used, they must pass an adequate amount of water to meet
pump suction requirements should the water in the pool drop below the weir
level. The equalizer pipes must be located at least 1 foot below the lowest
overflow level of the skimmer. A valve or equivalent device that will remain
tightly closed under normal operating conditions, but automatically opens when
the water level drops below the minimum operating level of the skimmer, must be
provided on each equalizer pipe. Equalizer lines must have covers that comply
with the American Society of Mechanical Engineers/American National Standards
Institute (ASME/ANSI) A 112.19.8-2007 or -2008 or other standard approved under
the federal Virginia Graeme Baker (VGB) Act.
005.11(G)(ii)(6)
BALANCING. The recirculation system must be balanced
to provide for optimum and uniform skimming.
005.11(H)
MAIN DRAIN SYSTEM AND
SUCTION OUTLETS. Main drains of the pool must be installed in the
pool floor at the deepest point, and must comply with American Society of
Mechanical Engineers/American National Standards Institute (ASME/ANSI) A
112.19.8-2007 or -2008 or other standard approved under the federal Virginia
Graeme Baker (VGB) Act.
005.11(H)(i)
NUMBER. 2 or more main drains or suction outlets, or a
single unblockable main drain or suction outlet must be installed. Dual main
drains or suction outlets must be connected in parallel, and must not permit
any drain to be individually valved off.
005.11(H)(ii)
SPACING. Dual main drains or suction outlets must be
at least 3 feet apart but not greater than 20 feet on centers, and main drains
must be provided not more than 15 feet from each side wall.
005.11(H)(iii)
FIELD FABRICATED
MAIN DRAINS OR SUCTION OUTLETS. Must be certified by a design
professional per American Society of Mechanical Engineers/American National
Standards Institute (ASME/ANSI) A 112.19.8-2007 or -2008 or other standard
approved under the federal Virginia Graeme Baker (VGB) Act. The open area of
the grate must not exceed 1.5 feet per second. Openings in grates must not be
over 1/2-inch wide. Gratings must not be removable without the use of tools.
005.11(H)(iv)
PIPING. The main drains and associated piping must
carry 100 percent of the recirculation rate, and must be equipped with a
valve.
005.11(I)
ANTI-ENTRAPMENT FOR EXISTING POOLS.
005.11(I)(i) All pools must be equipped with
anti-entrapment devices or systems that comply with the American Society of
Mechanical Engineers/American National Standards Institute (ASME/ANSI) A
112.19.8-2007 or -2008 performance standard, or any other standard approved
under the federal Virginia Graeme Baker (VGB) Act; and
005.11(I)(ii) All pools with a single main
drain other than an unblockable drain must be equipped, at a minimum, with 1 or
more of the following devices or systems designed to prevent entrapment by pool
or spa drains that meets the safety requirements of any American Society of
Mechanical Engineers/American National Standards Institute (ASME/ANSI)
performance standard if there is such a standard for such device or system, or
any applicable consumer product safety standard:
005.11(I)(ii)(1)
SAFETY VACUUM
RELEASE SYSTEM. A system which ceases operation of the pump,
reverses the circulation flow, or otherwise provides a vacuum release at a
suction outlet when a blockage is detected, that has been tested by an
independent third party and found to conform to American Society of Mechanical
Engineers/American National Standards Institute (ASME/ANSI) standard A
112.19.17-2007 or American Society for Testing and Materials (ASTM) standard
F2387;
005.11(I)(ii)(2)
SUCTION-LIMITING VENT SYSTEM. A system with a
tamper-resistant atmospheric opening;
005.11(I)(ii)(3)
GRAVITY DRAINAGE
SYSTEM. A system that utilizes a collector tank;
005.11(I)(ii)(4)
AUTOMATIC PUMP
SHUT-OFF SYSTEM. An automatic pump shut-off system;
005.11(I)(ii)(5)
DRAIN
DISABLEMENT. A device that disables the drain may be allowed per a
design professional's certification and Department review and approval;
and
005.11(I)(ii)(6)
OTHER SYSTEMS. Any other system determined by the
Department to be at least as effective as the systems described in items
005.11(I)(ii)(1)
through
005.11(I)(ii)(5)
above at preventing or eliminating the risk of injury or death associated with
pool drainage systems.
005.11(J)
PUMPS AND
STRAINERS.
005.11(J)(i)
STRAINERS. A cleanable strainer must be provided on
all pressure filter systems before entering the pump. The strainer must have a
quick-opening cover. At least 1 spare strainer basket must be provided. In
systems where the filter is located on the suction side of the pump, strainers
are not required.
005.11(J)(ii)
PUMPING EQUIPMENT. A pump and motor must be provided
for the recirculation of the swimming pool water. The pump must provide the
recirculation flow rate, and the filter backwash rate unless a separate
backwash pump is provided against the total dynamic head generated in the
recirculation system. The pump must be self-priming or must be installed so
that there is a net positive suction head on the pump inlet whenever the pump
is operating. The Department may allow multiple pumps. A gauge which indicates
pressure or vacuum, as appropriate, must be installed on the pump suction
header, and a pressure gauge must be installed on the discharge side of the
pump.
005.11(J)(iii)
ACCESSIBILITY. Pumps and motors must be readily
accessible for inspection and service.
005.11(K)
FLOW MEASUREMENT AND
CONTROL.
005.11(K)(i)
FLOW MEASUREMENT. A flow meter or which gives a
continuous indication of the flow rate in gallons per minute in the
recirculation system must be provided. Flow meters must have a measurement
capacity of at least 1.5 times the design recirculation flow rate, and must be
accurate within 10% of the actual flow rate. The indicator must have a range of
readings appropriate for the anticipated flow rates, and be installed where it
is readily accessible for reading and maintenance, and with straight pipe
upstream and downstream of any fitting or restriction in accordance with the
manufacturer's recommendation.
005.11(K)(ii)
FLOW
REGULATION. A valve must be provided in the recirculation pump
discharge piping.
005.11(L)
INLETS.
005.11(L)(i)
INLETS.
The recirculation system must have inlets and must be based on a minimum of 1
return inlet per 300 square feet of pool surface area or fraction thereof. Wall
inlets must be spaced not over 20 feet apart, with 1 inlet within 5 feet of
each corner of the pool and 1 in each recessed step area.
005.11(L)(ii)
LOCATION. Wall inlets must be located at least 12
inches below the design water surface, or not less than 6 inches if designed to
provide downward flow. Bottom inlets must be uniformly spaced, with a
separating distance of no greater than 20 feet.
005.11(L)(iii)
TYPE.
Inlet fittings must be of the adjustable rate-of-flow type. Directional flow
inlets must be used with skimmer-type pools. Floor inlets must not project from
the pool floor. Wall inlets must not extend from the wall more than 2
inches.
005.12
FILTRATION.
At least one filter must be provided that bears the American National Standard
Institute/National Sanitation Foundation (ANSI/NSF) Standard 50 certification
mark or be certified to ANSI/NSF Standard 50 by an organization accredited by
the American National Standards Institute. They must be installed with adequate
clearance and facilities for ready and safe inspection, maintenance,
disassembly and repair.
005.12(A)
SAND FILTERS.
005.12(A)(i)
FILTER
RATE. The design filtration rate of rapid sand filters must not
exceed 3 gallons per minute per square foot of filter area. High-rate sand
filters must not exceed a filtration rate of 15 gallons per minute per square
foot. Higher rates may be used if the filter has been successfully tested
against American National Standard Institute/National Sanitation Foundation
(ANSI/NSF) Standard 50 at the higher rate. The sand filter system must be
equipped to backwash each filter at a rate of 15 gallons per minute per square
foot of filter bed area, or as recommended by the manufacturer. A flow meter or
other device which gives a continuous indication of the flow rate in gallons
per minute to indicate the backwash rate for rapid sand filters must be
provided. The backwash water must be discharged to waste through a suitable air
gap.
005.12(A)(ii)
FILTER MEDIA. Sand or other media must be carefully
graded and meet the manufacturer's recommendation for pool use.
005.12(A)(iii)
ACCESSORIES. Accessories must include both an influent
pressure gauge and an effluent pressure gauge or a differential pressure gauge,
a backwash sight glass, and an air relief valve. When required the filter
system must have valving and piping to allow isolation, drainage, and
backwashing of individual filters.
005.12(B)
DIATOMACEOUS EARTH (DE)
TYPE FILTERS.
005.12(B)(i)
FILTER RATE. The design filtration rate for pressure
or vacuum filters must be not greater than 2 gallons per minute per square foot
of effective filter area, except that a maximum filtration rate of 2.5 gallons
per minute per square foot may be allowed for vacuum diatomaceous earth (DE)
filters only where continuous "body feed" is provided.
005.12(B)(ii)
PRECOATING. The filter piping must be designed to
refilter or waste the effluent until a uniform body coat is applied.
005.12(B)(iii)
REGENRATIVE-TYPE
FILTERS. Regenerative-type filters must meet the same standards as
other pressure filters. Bumping or agitating by air or manual means must be
provided for, and provision for inspection of elements must be
provided.
005.12(B)(iv)
ACCESSORIES. Accessories for vacuum filters must
include a vacuum gauge and a vacuum limit switch interconnected with the pump.
Pressure filters require a backwash sight glass, effluent pressure gauge,
influent pressure gauge and air relief valve. Valving and piping must be
provided to allow isolation, drainage, and backwashing of individual filters,
if needed for proper operation.
005.12(C)
CARTRIDGE-TYPE
FILTERS.
005.12(C)(i)
FILTER RATE. The design filtration rate for
surface-type cartridge filters must not exceed 0.375 gallons per minute per
square foot.
005.12(C)(ii)
CLEANING AND DISINFECTION. Equipment and facilities
must be provided for cleaning and disinfection of filter elements.
005.12(C)(iii)
ACCESSORIES. Accessories must include both an influent
and an effluent pressure gauge or a differential pressure gauge and an air
relief valve.
005.12(C)(iv)
SPARE CARTRIDGE. An extra set of cartridges, with at
least 100% filter area, must be provided.
005.13
DISINFECTION AND CHEMICAL
APPLICATION.
005.13(A)
CHEMICAL FEED EQUIPMENT. Feeders must withstand wear,
corrosion or attack by chemicals. The design must minimize potential for
blockage.
005.13(A)(i)
INTENDED
USE. The chemical feeder must only use chemicals recommended by
the manufacturer.
005.13(A)(ii)
SAFEGUARDS. The feeders must incorporate antisiphon
safeguards so that the chemical cannot continue to feed if any type of failure
of the pool equipment occurs. Chemical feed systems must be designed to prevent
chemical feed when water is not flowing from the recirculation system to the
pool.
005.13(A)(iii)
CYANURIC ACID AND INDOOR POOLS.
005.13(A)(iii)(1) Cyanuric acid will not be
allowed in new indoor pools.
005.13(A)(iii)(2) When replaced, a chemical
feed system must not use cyanuric acid.
005.13(B)
DISINFECTION. Swimming pools must be designed to
provide for continuous disinfection of the pool water with a chemical which is
an effective disinfectant, and which imparts an easily measured, active
residual.
005.13(B)(i)
DISINFECTANT FEEDERS. An automatic feeder which is
easily adjustable must be provided for the continuous application of
disinfectant.
005.13(B)(ii)
CAPACITY. Feeders must be capable of supplying
disinfectant at a rate of 0.1 pound per day chlorine (or equivalent) per gallon
per minute recirculation flow. This equates to a minimum of 8 parts per million
in the recirculation flow.
005.13(B)(iii)
HYPOCHLORINATORS. Where hypochlorinators are used,
feed must be capable of being continuous under all conditions of pressure in
the recirculation system.
005.13(B)(iv)
OTHER
DISINFECTANTS. Feed equipment must bear the American National
Standard Institute/National Sanitation Foundation (ANSI/NSF) -50 certification
mark or be certified to ANSI/NSF Standard 50 by an organization accredited by
the American National Standards Institute and must be installed in accordance
with the manufacturer's instructions.
005.13(B)(v)
TEST
EQUIPMENT. The owner of each swimming pool must have at least the
following testing equipment at the pool:
005.13(B)(v)(1)
CHLORINE/BROMINE
TEST KIT OR FERROUS AMMONIUM SULFATE-DIETHYL-P-PHENYLENE DIAMINE (FAS-DPD) TEST
KIT. If other halogens are used, an appropriate scale must be
provided. Electronic residual monitoring devices may be used in addition to the
test kit.
005.13(B)(v)(2)
pH TEST KIT. A pH test kit with a range from 7.0 to
8.0, accurate to the nearest 0.2 pH unit.
005.13(B)(v)(3)
ALKALINITY TEST
KIT. The alkalinity test range must be at least 60 to 400 parts
per million (mg/L) as CaCO3.
005.13(B)(v)(4)
CYANURIC ACID
TEST KIT. Where cyanurates are used, a test kit to measure the
cyanuric acid concentration must be provided. It must permit readings to at
least 100 parts per million (mg/L) with maximum increments of 25 parts per
million (mg/L).
005.14
BATHHOUSE.
005.14(A)
GENERAL.
All Class A pools must have a bathhouse with dressing, shower, and sanitary
facilities. All class B, C, D, E, and F swimming pools are required to have
minimum sanitary facilities consisting of toilets and sinks. Omission of part
or all of the pool-side shower and toilet facilities may be approved by the
Department when adequate facilities are conveniently available as determined by
the Department.
005.14(B)
DESIGN CRITERIA.
005.14(B)(i)
BATHHOUSE
ROUTING. The location of the bathhouse must be adjacent to the
pool.
005.14(B)(ii)
BATHHOUSE DESIGN. Floors of the bathhouse must be of
smooth-finish material with slip-resistant surface, impervious to moisture,
easily cleanable and sloped at least 1/4 inch per foot to drains. Carpeting is
not permitted in shower and toilet areas.
005.14(B)(iii)
FIXTURE
REQUIREMENTS. Unless approved pursuant to 178 NAC
2-005.14(A),
bathhouse facilities must be provided based on maximum patron load designed for
the swimming pool per Table 3. Fixtures provided in family changing rooms or
other unisex restroom facilities which are available to swimming pool patrons
may be included in the required male or female fixture count, but not both.
Fixture Requirement Table 3
Fixtures Required Male
|
Fixtures Required Female
|
Total Patron Load
|
Toilets
|
Urinals
|
Sinks
|
Showers
|
Toilets
|
Sinks
|
Showers
|
0-50
|
1
|
1
|
1
|
1
|
2
|
1
|
1
|
51-100
|
1
|
1
|
1
|
1
|
2
|
1
|
1
|
101-150
|
1
|
2
|
1
|
2
|
3
|
1
|
2
|
151-200
|
1
|
2
|
1
|
2
|
3
|
1
|
2
|
201-250
|
2
|
2
|
1
|
3
|
4
|
2
|
3
|
251-300
|
2
|
3
|
2
|
4
|
5
|
2
|
4
|
301-400
|
2
|
3
|
2
|
5
|
5
|
2
|
5
|
401-500
|
3
|
3
|
2
|
6
|
6
|
2
|
6
|
501-1000
|
3
|
4
|
2
|
7
|
7
|
2
|
7
|
1001-1500
|
4
|
5
|
2
|
10
|
9
|
2
|
10
|
1501-2000
|
5
|
6
|
2
|
15
|
11
|
2
|
15
|
2001 or more
|
6
|
7
|
3
|
20
|
13
|
3
|
20
|
005.14(B)(iv)
HOSE
BIBS. Hose bibs with a back-siphonage device must be provided to
enable the entire bathhouse area to be flushed.
005.15
MISCELLANEOUS.
005.15(A)
POOL CLEANING
SYSTEM. A system must be provided to remove dirt and other foreign
material from the pool. Built-in vacuum lines must not be used.
005.15(A)(i)
STARTING
BLOCKS. Starting blocks, when provided, must be located where the
water depth is at least 5 feet and must be removable.
005.15(A)(ii)
SAND AREA RINSE
SHOWERS. Sand areas are not allowed inside the pool enclosure
unless separated by an effective barrier to control access to the swimming pool
deck. Persons entering the swimming pool from the sand area must pass a water
spray or shower. Drainage must not be directed to the pool.
005.15(A)(iii)
BOILERS. Where boilers are provided, the design
professional must ensure that they meet the Boilers Inspection Act, Neb. Rev.
Stat. §§
48-719
through
48-743.
005.16
SPRAY PARKS. Except as modified by 178 NAC 2-005.16,
compliance is required with all other applicable portions of 178 NAC 2-005. A
spray park includes no standing water and uses potable water that is
recirculated and treated or from the deep area of a swimming pool. A play area
with sprays or other features that uses only potable water that is not
circulated is not included in this definition.
005.16(A)
GENERAL.
005.16(A)(i)
SURFACE
MATERIAL. The surface of a spray park must be impervious and
durable. Padding specifically designed for water features must be water
resistant or must permit full drainage without retaining water in its
structure. Walking surfaces must be slip-resistant.
005.16(A)(ii)
SURFACE
SLOPES. The splash zone must be properly sloped so that only water
from the sprays flows back to the drains. Areas adjacent to the splash zone
must be sloped away from the collection drains. Plants or vegetation within the
immediate area of the splash zone are prohibited.
005.16(A)(iii)
SPRAY PARK
DRAINS. Must not be directly connected to a pump. At least 2
drains must be provided. The openings in the drain covers must be no wider than
½ inch. Drain covers must be securely fastened to the drain structure so
that they cannot be removed without tools. Drains and the associated piping
must be designed for 125% of the flow into the spray park (play feature and
recirculation, as applicable).
005.16(A)(iv)
PLAY
FEATURES.
005.16(A)(iv)(1)
SURFACE SPRAYS. Must be flush with the spray park
surface. Spray openings must be ½ inch or less.
005.16(A)(iv)(2)
ABOVE GROUND
FEATURES. Must not present a tripping hazard. Features must not
have sharp edges or points, or rough surfaces and must be of
corrosion-resistant materials or coating.
005.16(A)(iv)(3)
ATMOMIZED
MISTS. All sprays that produce finely atomized mists must be
connected to a separate potable water source.
005.16(B)
WATER TREATMENT
TANK. The recirculation system must be independent from any
adjacent swimming pool. The recirculation system components and design must
comply with all other applicable parts of 178 NAC 2-005 except as modified by
178 NAC 2-005.16.
005.16(B)(i)
WATER VOLUME. Must be 5 minutes of the flow in gallons
per minute of the spray features and the recirculation system combined or 4,000
gallons, whichever is the larger volume.
005.16(B)(ii)
RATE.
A 30 minute turnover must be provided.
005.16(B)(iii)
TANK
VOLUME. Must have a volume of at least 125% of the volume
specified in 178 NAC
2-005.16(B)(i).
The tank must be accessible for cleaning and inspection.
005.16(B)(iii)(1)
DRAIN. Must be provided with a drain to waste and not
directly connected to a sanitary system. .
005.16(B)(iii)(2)
AUTOMATIC LEVEL
CONTROL. The water level must be automatically maintained at the
overflow level.
005.16(B)(iv)
SEPARATE
SYSTEMS. The recirculation treatment system and the play feature
pump(s) and piping must be separate. The play feature pump system must not
operate if the recirculation system pump is not operating.
005.16(B)(v)
PLAY FEATURE
PIPING. The play feature pump suction and return line to the water
storage tank must be designed to prevent short-circuiting. The suction intake
for the recirculation pump must be located in the lowest portion of the water
treatment tank. Play features and piping must automatically drain into the
water treatment tank when the play features are not operating. An easily
readable flow meter that complies with the requirements of 178 NAC
2-005.11(K)(i)
must be installed in the play feature circulation system.
005.16(B)(vi)
TREATED WATER
DISTRIBUTION. The water storage tank must be designed to maintain
water quality as outlined in 178 NAC
2-006.
005.16(B)(vii)
SAMPLE
TAP. A sample tap must be available in the equipment area for the
play feature piping.
005.17
FOUNTAINS, SPRAYS, OR
SIMILAR FEATURES. Are permitted only in water depths not exceeding
2 feet. These features must be of a nonclimbable design, unless specifically
manufactured as a climbing structure. Water supplied to these fountains must
come from the recirculation system after filtration. Water supplied to these
fountains may also come from the deepest portion of the main swimming pool
excluding the surge tank, main drain, gutters, skimmers, and depths of less
than 2 feet. Dedicated wading or zero depth pools not exceeding 2 feet in depth
must use filtered water.
005.18
BRIDGES AND OVERHEAD OBSTRUCTIONS. The minimum height
of the bridge or obstruction must be at least 8 feet from the bottom of the
pool and at least 4 feet above the surface of the pool. Minimum 42-inch high
handrails must be provided along each side of the bridge. The walking surfaces
must be constructed of concrete or other nonabsorbent material having a smooth
slip-resistant finish.
005.19
SPAS. A spa is not intended to be drained, cleaned,
and refilled after each individual use. It may include, but not be limited to,
hydrojet circulation, hot water, cold water, mineral baths, air induction
systems, or any combination thereof. A pool used under direct supervision of
licensed healthcare professionals is excluded.
005.19(A)
GENERAL.
Requirements for conventional swimming pools may be modified for spas at the
discretion of the Department. Except as modified by 178 NAC 2-005.19,
compliance is required with all other applicable sections of 178 NAC 2-005.
005.19(B)
PHYSICAL
SEPARATION. A spa must be physically separated from any other
swimming pool.
005.19(C)
PATRON LOAD. The patron load must not exceed 1 person
per 3 lineal feet of seat or bench measured at the front edge.
005.19(D)
MAXIMUM
DEPTHS. The maximum water depth must be 4 feet measured from the
water line. The maximum depth of any seat or sitting bench must be 2 feet
measured from the water line.
005.19(E)
STAIRS, LADDERS, AND
RECESSED TREADS. Must be provided when spa depths are greater than
2 feet. A spa must be equipped with at least 1 means of egress with handrails
for each 50 feet of perimeter or portion thereof.
005.19(F)
DECK
WIDTHS. A 5 foot minimum width, continuous, unobstructed deck,
which may include the coping, must be provided on 50% or more of the spa. When
the spa is adjacent to another pool, the spa must be located at the shallow
end, with a minimum distance of 5 feet between the 2 bodies of water.
005.19(G)
WATER
TEMPERATURE CONTROLS. Must be provided to prevent water
temperatures in excess of 104 degrees Fahrenheit (40°C) and must be
accessible only to a Nebraska swimming pool operator.
005.19(H)
SPA
DRAINAGE. The spa must be equipped to completely drain. Water
suction outlets must conform to 178 NAC
2-005.11(H) or 178
NAC
2-005.11(I).
005.19(I)
SURFACE
SKIMMERS. 1 surface skimmer must be provided for each 100 square
feet or major fraction thereof of surface area.
005.19(J)
RECIRCULATION SYSTEM
INLETS. A minimum of 2 inlets must be provided.
005.19(K)
AIR INDUCTION
SYSTEMS. An air induction system, must prevent water back-up that
could cause electrical shock hazards. Air intake sources must not permit the
introduction of toxic fumes or other contaminants.
005.19(L)
DISINFECTANT
FEEDERS. Gas chlorinators must not be used.
005.19(M)
RECIRCULATION
RATE. The recirculation rate must provide 30 gallons per minute
per skimmer, or provide a 30-minute turnover, whichever provides a greater flow
rate.
005.19(N)
AGITATION SYSTEMS. The agitation system must be
connected to a timer located out of reach ofpersons in the spa. The timer must
not exceed 15 minutes.
005.19(O)
EMERGENCY SHUTOFF. Must be located within sight of the
spa, at least 5 feet horizontally from the inside walls of the spa, and must be
clearly labeled. This control must disable all spa circulation, agitation, air
induction systems, as well as other associated mechanical, chemical feed and
electrical devices.
005.19(P)
ROOFS OR CANOPIES OVER SPA. Must be constructed so
that moisture or condensation from the roof or canopy will not drain into the
spa. Where a roof or canopy covers the spa, the height from the rim of the spa
to the lowest point of the canopy must be at least 7-1/2 feet.
005.19(Q)
HEATING.
All room heating units must be isolated or protected from contact with spa
users to prevent injury. The spa room-heating unit must be capable of
maintaining a temperature of 75°F to 82°F.
005.19(R)
THERMOMETER. An in-line thermometer on the spa water
return line is required.
005.20
WADING POOLS.
005.20(A)
GENERAL.
Except as modified by 178 NAC 2-005.20, compliance is required with all other
applicable parts of 178 NAC 2-005.
005.20(B)
RECIRCULATION.
005.20(B)(i)
RATE.
The recirculation rate must provide a turnover of 1 hour or less.
005.20(B)(ii)
SEPARATE
SYSTEM. A wading pool must have a separate recirculation system
from other swimming pools.
005.20(B)(iii)
SURFACE
SKIMMING. Intermittent fixed weir overflow structures, including
gutters, scuppers, and drains at zero depth may be used. The overflow system
must have a hydraulic capacity of at least 125 percent of the recirculation
flow rate.
005.20(B)(iv)
SKIMMER EQUALIZER LINE. May be connected to the main
drain.
005.20(B)(v)
INLETS. Inlets must be located to distribute treated
water to all parts of the wading pool and to move debris to the overflow and
drain systems.
005.20(C)
SAFETY.
005.20(C)(i)
BARRIER AND LOCATION. When a wading pool is in the
same enclosure as a supervised swimming pool, it must be near the shallow end
of the pool, and there must be a barrier at least 3 feet high between the
wading pool and the swimming pool with a self-closing, self-latching
gate.
005.20(C)(ii)
BARRIER. Stand-alone wading pools or wading pools
associated with unsupervised swimming pools must have a barrier, as required by
178 NAC 2-005.08.
005.20(C)(iii)
DEPTH MARKING. Signs must be provided at the pool
indicating the maximum depth in addition to other required depth
markings.
005.20(C)(iv)
STEPS OR LADDERS. Steps or ladders are not required at
wading pools.
005.21
WAVE POOLS.
Pools with wave generating equipment and a design which provides for control of
the waves within the side walls and dissipation of the waves at a zero depth
shallow end.
005.21(A)
GENERAL. Requirements for conventional swimming pools
may be modified for wave pools at the discretion of the Department. Except as
modified by 178 NAC 2-005.21, compliance is required with all other applicable
sections of 178 NAC 2-005.
005.21(B)
GUTTERS.
Overflow gutters must be provided, but may be omitted along the side of the
pool with the wave generating equipment if effective skimming devices are
provided instead. Continuous skimming must be provided during the quiescent
period over the entire length of the gutter. The zero depth end must have a
continuous trench with a grate.
005.21(C)
DECKS AND
LADDERS.
005.21(C)(i)
BARRIERS. A safety railing or other effective barrier
at least 42 inches in height must be provided to prevent swimmers from entering
the pool at any location other than the zero water depth end. It must have at
least 1 intermediate-height rail or rope.
005.21(C)(ii)
RUNOUT. Runout areas sloping down toward the zero
depth trench must not exceed 4 feet.
005.21(C)(iii)
ACCESS. Deck areas accessible to swimmers may be
omitted along the side of the pool with the wave generating
equipment.
005.21(C)(iv)
LADDERS. Ladders must be of a recessed
design.
005.21(D)
WAVES.
005.21(D)(i)
MAGNITUDE. The wave generating equipment must not be
capable of producing waves of a magnitude which could cause swimmers to have
contact with the pool bottom in the deep end.
005.21(D)(ii)
EMERGENCY
SHUTOFF. An emergency shutoff for the wave generating equipment
must be provided at every lifeguard chair at a minimum. At least 4 emergency
shutoffs must be provided.
005.21(E)
OPENINGS.
005.21(E)(i)
INLET.
The zero depth area must have bottom inlets.
005.21(E)(ii)
OPENINGS TO WAVE
GENERATING EQUIPMENT. Openings to wave generating equipment must
be designed to prevent entrapment of swimmers.
005.22
ZERO DEPTH
POOLS.
005.22(A) GENERAL. Except
as modified by 178 NAC 2-005.22, zero depth pool facilities must comply with
all other applicable provisions of 178 NAC 2-005.
005.22(B)
ZERO DEPTH
END. A gutter or trench with a grate cover is required along all
zero depth areas. It must be at an elevation that allows effective skimming at
the trench at all times.
005.22(C)
RUNOUT. Runout areas sloping toward the zero depth
trench must not exceed 6 feet.
005.22(D)
BOTTOM
INLETS. A system of bottom inlets must be provided in the shallow
end, designed to provide the minimum of a 2-hour turnover for that
area.
005.23
POOL SLIDES. All slides used at pools must be
specifically designed and intended for use with a pool. An emergency shutdown
control must be provided for all water slides. This control must stop all water
flow on the slide and must be mounted in the pool area, no more than 50 feet
from the slide for lifeguards or for slide users. Water slides require special
consultation with the Department for consideration of design variations and
areas where potential problems may exist. Requirements for swimming pools may
be modified for water slides at the discretion of the Department. Except as
modified by 178 NAC 2-005.23, compliance is required with all other applicable
sections of 178 NAC 2-005.
005.23(A)
ENTRY. Slide entry areas must be designed so the rider
is able to properly enter and position himself or herself before sliding down
the chute. This area must be a small platform or a less-sloped portion of
chute, with well-placed assist bars.
005.23(B)
HANDRAILS.
Slides must have handrails on both sides of the ladder or steps. Platforms and
landings must have guardrails not less than 42 inches high, with an effective
barrier such that a 4-inch diameter sphere cannot pass through. Handrail height
must not be less than 34 inches and not more than 38 inches high, with
balusters or ornamental patterns such that a 4-inch diameter sphere cannot pass
through.
005.23(C)
PUMP
INTAKE. Water from the surge tank and water leaving the pool for
recirculation (for example, main drain, gutter, skimmers, and main drain line)
must not be used for pump intakes.
005.23(D)
CHILDREN'S ACITIVITY
SLIDES. Children's activity slides are small slides with a low
exit velocity designed by the manufacturer for use by small children at pools.
They must be designated by the manufacturer for use in 24 inches or less of
water.
005.23(E)
DROP
SLIDES. A drop slide discharges to a pool with a drop of more than
2 inches to the water surface.
005.23(E)(i)
LANDING AREA. There must be a drop slide landing area
extending 5 feet on either side of the center line of the slide and from the
back wall to 20 feet in front of the slide terminus. This area must not
infringe on the required landing areas for other pool equipment.
005.23(E)(ii)
LANDING AREA
DESIGNATION. The landing area must be clearly designated by float
ropes. A slide mounted in a separate diving area may be allowed to use the
diving area separation as long as access to the diving well is restricted to
patrons using the slide and diving equipment.
005.23(E)(iii)
SLIDE
TERMINUS. The terminus of the chute must extend beyond the pool
wall, and must not interfere with the safety area of other pool
equipment.
005.23(E)(iv)
EXIT ANGLE. The maximum angle of the slide runway at
the exit must be between 0 degrees and 11 degrees, measured downward from
horizontal.
005.23(E)(v)
WATER DEPTH. The area from the slide terminus outward
6 feet in front of the slide terminus must have a depth as established from the
table below. The slide must be constructed so the rider enters the water in
this 6-foot area. If the depth is 5 feet or less, the bottom in this area must
have a maximum slope of 1 inch in 12 inches (1:12), and the slide must be
located at least 5 feet from any change to steeper slope of the pool bottom.
Water Depth from the Slide Terminus to 6 Feet in
Front of the Terminus (see above)
|
Corresponding Maximum Exit Height Above the
Water
|
4 feet minimum
>4 to 8 feet minimum
|
2 to 12 inches
greater than 12 to 42 inches (Subject to
interpolation)
|
005.23(E)(vi)
MAXIMUM
DROP. The maximum drop height at the terminus of the slide must
not exceed 42 inches.
005.23(F)
FLUME
SLIDES. A flume slide consists of 1 or more flumes entering a
plunge pool or dedicated plunge area of a multiple use pool at or near the
water level.
005.23(F)(i)
FLUMES.
005.23(F)(i)(1)
POSITION. A flume must be perpendicular to the plunge
pool wall for a distance of at least 10 feet from the exit end of the
flume.
005.23(F)(i)(2)
CLEARANCE. The distance between the side of a flume
terminus and a plunge pool side wall must be at least 4 feet. The distance
between sides of adjacent flume terminuses must be at least 6 feet. The
distance between a flume exit end and the opposite side of the plunge pool,
excluding steps, must be at least 20 feet.
005.23(F)(i)(3)
ELEVATION. A flume must terminate at a depth between 6
inches below the plunge pool operating water surface level and 2 inches above
the water surface level. The flume must not exceed a 1-in-ten slope for a
distance of at least 10 feet from its exit end.
005.23(F)(i)(4)
DESIGN. The design of the flume must minimize abrupt
contact with the slide and prevent people from being
airborne.
005.23(F)(ii)
PLUNGE POOLS.
005.23(F)(ii)(1)
DEPTHS. The plunge pool operating water depth at the
end of a flume must be 3 to 4 feet. A depth of at least 3 feet must be
maintained in front of the flume for a distance of at least 10 feet, from which
the pool floor may have a constant slope upward.
005.23(F)(ii)(2)
PLUNGE
AREA. The plunge area in multi-use pools must be designated by
float ropes, and each area must have ladders, steps, or stairs for
egress.
005.23(F)(iii)
FLUME PUMPS.
005.23(F)(iii)(1)
CHECK
VALVES. Each flume pump discharge pipe must have a check
valve.
005.23(F)(iii)(2)
WALKWAYS. A 4-foot minimum width, surfaced walkway or
steps must be provided between the plunge pool deck and the steps leading to
the top of the flume(s).
005.23(F)(iii)(3)
PUMP
RESERVOIR. If a separate pump reservoir is provided, it must have
a main drain and surface skimmer, both connected to the recirculation
system.
005.24
LAZY RIVER
RIDES. Except as modified by 178 NAC 2-005.24, compliance is
required with all other applicable parts of 178 NAC 2.
005.24(A)
CONSTRUCTION
MATERIAL. Lazy River Rides must be constructed of concrete or
other impervious materials with a nontoxic, smooth and slip-resistant finish.
These rides must be of such shape and design as to be operated in a safe and
sanitary manner.
005.24(B)
WATER DEPTH. The maximum water depth of the Lazy River
Ride must not exceed 4 feet.
005.24(C)
DECKS.
Decking must be provided at the entrance and exit points as necessary to
provide safe patron access but must not be smaller than 10 feet in width and
length. Additional decking along the ride course is not required except that
decking is required at lifeguard locations and emergency exit points.
005.24(D)
EMERGENCY EXIT
LOCATIONS. Access and exit must be provided at the start and end
of the ride only, except that emergency exit locations may be located along the
ride course as necessary to provide for the safety of the patrons.
005.24(E)
PATRON
LOADING. 25 square feet of Lazy River water surface area must be
provided for each patron.