Current through September 17, 2024

In new construction, the licensee must:

(A) Provide a conveniently located sink for soaking and hand washing of laundry when laundry services are provided on-site at the children's day health service;

(B) Ensure the door of a toilet, changing, or bathing room with less than 50 square feet of clear floor area and dedicated to consumer use must not swing inward;

(C) Ensure curtain layout must totally surround each care and treatment location which will not restrict access to the entrance to the room, lavatory, toilet, or enclosed storage facilities;

(D) Ensure electrical systems have ground fault circuit interrupter protected outlets in all wet areas and within 6 feet of all hand washing sinks;

(E) Ensure mechanical exhaust ventilation at a rate of 10 air exchanges per hour for windowless toilets, changing and bathing areas, laundry rooms, housekeeping rooms, and kitchens; and

(F) Ensure mechanical exhaust ventilation at a rate of 5 air exchanges per hour for care, treatment, and service areas.

Disclaimer: These regulations may not be the most recent version. Nebraska may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.